Passage Data · Check a report · Use it from your AI
Sewage treatment plant, Brownsboro, Texas. NPDES permit TX0062707, in force until Mar 24, 2027. Last 12 months: over a limit 21 times (last August 2026), 10 of 11 reports late. Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| October 2025 | E. coli, daily average | 913 CFU/100mL | ≤ 126 CFU/100mL | 625% |
| October 2025 | E. coli, single grab sample | 1990 CFU/100mL | ≤ 399 CFU/100mL | 399% |
| November 2025 | E. coli, daily average | 1062 CFU/100mL | ≤ 126 CFU/100mL | 743% |
| November 2025 | E. coli, single grab sample | 2420 CFU/100mL | ≤ 399 CFU/100mL | 507% |
| December 2025 | E. coli, daily average | 2420 CFU/100mL | ≤ 126 CFU/100mL | 1821% |
| December 2025 | E. coli, single grab sample | 2420 CFU/100mL | ≤ 399 CFU/100mL | 507% |
| January 2026 | E. coli, daily average | 886 CFU/100mL | ≤ 126 CFU/100mL | 603% |
| January 2026 | E. coli, single grab sample | 2420 CFU/100mL | ≤ 399 CFU/100mL | 507% |
| February 2026 | E. coli, daily average | 204 CFU/100mL | ≤ 126 CFU/100mL | 62% |
| February 2026 | E. coli, single grab sample | 770 CFU/100mL | ≤ 399 CFU/100mL | 93% |
| March 2026 | E. coli, daily average | 854 CFU/100mL | ≤ 126 CFU/100mL | 578% |
| March 2026 | E. coli, single grab sample | 2419 CFU/100mL | ≤ 399 CFU/100mL | 506% |
| April 2026 | E. coli, single grab sample | 579 CFU/100mL | ≤ 399 CFU/100mL | 45% |
| May 2026 | E. coli, daily average | 1194 CFU/100mL | ≤ 126 CFU/100mL | 848% |
| May 2026 | E. coli, single grab sample | 2420 CFU/100mL | ≤ 399 CFU/100mL | 507% |
| June 2026 | E. coli, daily average | 610 CFU/100mL | ≤ 126 CFU/100mL | 384% |
| June 2026 | E. coli, single grab sample | 2419 CFU/100mL | ≤ 399 CFU/100mL | 506% |
| July 2026 | E. coli, daily average | 663 CFU/100mL | ≤ 126 CFU/100mL | 426% |
| July 2026 | E. coli, single grab sample | 1730 CFU/100mL | ≤ 399 CFU/100mL | 334% |
| August 2026 | E. coli, daily average | 448 CFU/100mL | ≤ 126 CFU/100mL | 256% |
| August 2026 | E. coli, single grab sample | 1300 CFU/100mL | ≤ 399 CFU/100mL | 226% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Oxygen, dissolved [DO] | monthly minimum | ≥ 4 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 30 mg/L | all year |
| BOD, 5-day, 20 deg. C | single grab sample | ≤ 100 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 39 lb/d | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, total suspended | daily average | ≤ 90 mg/L | all year |
| Solids, total suspended | daily average | ≤ 117 lb/d | all year |
| Nitrogen, ammonia total [as N] | daily average | report only (mg/L) | all year |
| Nitrogen, ammonia total [as N] | daily average | report only (lb/d) | all year |
| Flow, in conduit or thru treatment plant | daily average | ≤ .156 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| E. coli | daily average | ≤ 126 CFU/100mL | all year |
| E. coli | single grab sample | ≤ 399 CFU/100mL | all year |
Cited limits by parameter: Texas's rules and the federal ones.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/TX0062707 · MCP: https://passage-data.com/mcp