Passage Data · Check a report · Use it from your AI
Sewage treatment plant, Stockdale, Texas. NPDES permit TX0054232, in force until Mar 21, 2030. Last 12 months: over a limit 19 times (last August 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| October 2025 | BOD, 5-day, 20 deg. C, daily average | 38.25 mg/L | ≤ 30 mg/L | 28% |
| November 2025 | Solids, total suspended, daily average | 110 mg/L | ≤ 90 mg/L | 22% |
| December 2025 | BOD, 5-day, 20 deg. C, daily average | 37 mg/L | ≤ 30 mg/L | 23% |
| December 2025 | E. coli, daily average | 174 CFU/100mL | ≤ 126 CFU/100mL | 38% |
| December 2025 | Solids, total suspended, daily average | 114.6 mg/L | ≤ 90 mg/L | 27% |
| January 2026 | BOD, 5-day, 20 deg. C, daily average | 43.8 mg/L | ≤ 30 mg/L | 46% |
| January 2026 | E. coli, daily average | 275 CFU/100mL | ≤ 126 CFU/100mL | 118% |
| January 2026 | Solids, total suspended, daily average | 127.8 mg/L | ≤ 90 mg/L | 42% |
| February 2026 | BOD, 5-day, 20 deg. C, daily average | 34.25 mg/L | ≤ 30 mg/L | 14% |
| February 2026 | Solids, total suspended, daily average | 136.5 mg/L | ≤ 90 mg/L | 52% |
| March 2026 | Solids, total suspended, daily average | 130 mg/L | ≤ 90 mg/L | 44% |
| April 2026 | E. coli, daily average | 456 CFU/100mL | ≤ 126 CFU/100mL | 262% |
| April 2026 | E. coli, single grab sample | 2419 CFU/100mL | ≤ 399 CFU/100mL | 506% |
| April 2026 | Solids, total suspended, daily average | 126 mg/L | ≤ 90 mg/L | 40% |
| May 2026 | E. coli, daily average | 383 CFU/100mL | ≤ 126 CFU/100mL | 204% |
| May 2026 | E. coli, single grab sample | 980 CFU/100mL | ≤ 399 CFU/100mL | 146% |
| May 2026 | Solids, total suspended, daily average | 98 mg/L | ≤ 90 mg/L | 9% |
| July 2026 | Solids, total suspended, daily average | 101 mg/L | ≤ 90 mg/L | 12% |
| August 2026 | Solids, total suspended, daily average | 117.8 mg/L | ≤ 90 mg/L | 31% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Oxygen, dissolved [DO] | monthly minimum | ≥ 4 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 30 mg/L | all year |
| BOD, 5-day, 20 deg. C | single grab sample | ≤ 100 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 75 lb/d | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, total suspended | daily average | ≤ 90 mg/L | all year |
| Solids, total suspended | daily average | ≤ 225 lb/d | all year |
| Flow, in conduit or thru treatment plant | daily average | ≤ .3 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| E. coli | daily average | ≤ 126 CFU/100mL | all year |
| E. coli | single grab sample | ≤ 399 CFU/100mL | all year |
Cited limits by parameter: Texas's rules and the federal ones.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/TX0054232 · MCP: https://passage-data.com/mcp