Passage Data · Check a report · Use it from your AI

Cushing, City of

Sewage treatment plant, Cushing, Texas. NPDES permit TX0053937, in force until Jan 24, 2029. Last 12 months: over a limit 3 times (last June 2026). Source: EPA ECHO, Oct 22, 2026.

Reports due
About 20 days after each period: form A monthly (14 values)
Last report on file
August 2026
Oct 2024 – Sep 2025
3 values over a limit, 0 required values missing, 0 of 12 reports late

Last 12 months (Oct 1, 2025 – Sep 30, 2026)

Period endingParameterReportedLimitOver by
February 2026Chlorine, total residual, monthly maximum4.3 mg/L≤ 4 mg/L8%
June 2026E. coli, daily average770 CFU/100mL≤ 126 CFU/100mL511%
June 2026E. coli, single grab sample770 CFU/100mL≤ 399 CFU/100mL93%

Limits in force (14)

ParameterStatisticLimitMonths
Oxygen, dissolved [DO]monthly minimum≥ 4 mg/Lall year
BOD, 5-day, 20 deg. Cdaily average≤ 30 mg/Lall year
BOD, 5-day, 20 deg. Csingle grab sample≤ 100 mg/Lall year
BOD, 5-day, 20 deg. Cdaily average≤ 20 lb/dall year
pHminimum≥ 6 SUall year
pHmaximum≤ 9 SUall year
Solids, total suspendeddaily average≤ 90 mg/Lall year
Solids, total suspendeddaily average≤ 61 lb/dall year
Flow, in conduit or thru treatment plantdaily average≤ .081 MGDall year
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year
Chlorine, total residualmonthly minimum≥ 1 mg/Lall year
Chlorine, total residualmonthly maximum≤ 4 mg/Lall year
E. colidaily average≤ 126 CFU/100mLall year
E. colisingle grab sample≤ 399 CFU/100mLall year

How strict are these limits?

Cited limits by parameter: Texas's rules and the federal ones.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/TX0053937 · MCP: https://passage-data.com/mcp