Passage Data · Check a report · Use it from your AI
Sewage treatment plant, Cisco, Texas. NPDES permit TX0053716, in force until Feb 16, 2029. Last 12 months: over a limit 15 times (last May 2026), 1 of 11 reports late. Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| November 2025 | E. coli, daily average | 136.21 CFU/100mL | ≤ 126 CFU/100mL | 8% |
| December 2025 | BOD, 5-day, 20 deg. C, daily average | 35.87 mg/L | ≤ 30 mg/L | 20% |
| December 2025 | E. coli, daily average | 711.83 CFU/100mL | ≤ 126 CFU/100mL | 465% |
| December 2025 | E. coli, single grab sample | 1732.9 CFU/100mL | ≤ 399 CFU/100mL | 334% |
| January 2026 | BOD, 5-day, 20 deg. C, daily average | 40.95 mg/L | ≤ 30 mg/L | 37% |
| January 2026 | E. coli, daily average | 181.05 CFU/100mL | ≤ 126 CFU/100mL | 44% |
| January 2026 | E. coli, single grab sample | 1046.2 CFU/100mL | ≤ 399 CFU/100mL | 162% |
| February 2026 | BOD, 5-day, 20 deg. C, daily average | 37.875 mg/L | ≤ 30 mg/L | 26% |
| February 2026 | E. coli, daily average | 150.25 CFU/100mL | ≤ 126 CFU/100mL | 19% |
| March 2026 | BOD, 5-day, 20 deg. C, daily average | 53.55 mg/L | ≤ 30 mg/L | 79% |
| March 2026 | E. coli, daily average | 267.11 CFU/100mL | ≤ 126 CFU/100mL | 112% |
| March 2026 | E. coli, single grab sample | 686.7 CFU/100mL | ≤ 399 CFU/100mL | 72% |
| April 2026 | BOD, 5-day, 20 deg. C, daily average | 30.6 mg/L | ≤ 30 mg/L | 2% |
| April 2026 | E. coli, daily average | 242.23 CFU/100mL | ≤ 126 CFU/100mL | 92% |
| May 2026 | BOD, 5-day, 20 deg. C, daily average | 34.95 mg/L | ≤ 30 mg/L | 17% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Oxygen, dissolved [DO] | monthly minimum | ≥ 4 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 30 mg/L | all year |
| BOD, 5-day, 20 deg. C | single grab sample | ≤ 100 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 100 lb/d | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, total suspended | daily average | ≤ 90 mg/L | all year |
| Solids, total suspended | daily average | ≤ 300 lb/d | all year |
| Flow, in conduit or thru treatment plant | daily average | ≤ .4 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| E. coli | daily average | ≤ 126 CFU/100mL | all year |
| E. coli | single grab sample | ≤ 399 CFU/100mL | all year |
Cited limits by parameter: Texas's rules and the federal ones.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/TX0053716 · MCP: https://passage-data.com/mcp