Passage Data · Check a report · Use it from your AI
Sewage treatment plant, Avery, Texas. NPDES permit TX0053503, in force until Apr 2, 2031. Last 12 months: over a limit 9 times (last September 2026), 15 required values missing, 3 of 12 reports late. Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| May 2026 | Chlorine, total residual, monthly maximum | 4.13 mg/L | ≤ 4 mg/L | 3% |
| June 2026 | Chlorine, total residual, monthly minimum | .57 mg/L | ≥ 1 mg/L | 43% |
| June 2026 | Solids, total suspended, daily average | 16.93 mg/L | ≤ 15 mg/L | 13% |
| July 2026 | Chlorine, total residual, monthly maximum | 4.5 mg/L | ≤ 4 mg/L | 13% |
| July 2026 | Chlorine, total residual, monthly minimum | .7 mg/L | ≥ 1 mg/L | 30% |
| August 2026 | Chlorine, total residual, monthly maximum | 4.5 mg/L | ≤ 4 mg/L | 13% |
| August 2026 | Chlorine, total residual, monthly minimum | .7 mg/L | ≥ 1 mg/L | 30% |
| September 2026 | Chlorine, total residual, monthly maximum | 4.3 mg/L | ≤ 4 mg/L | 8% |
| September 2026 | Solids, total suspended, daily average | 29.48 mg/L | ≤ 15 mg/L | 97% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Oxygen, dissolved [DO] | monthly minimum | ≥ 4 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 10 mg/L | all year |
| BOD, 5-day, 20 deg. C | single grab sample | ≤ 35 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 10 lb/d | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, total suspended | daily average | ≤ 15 mg/L | all year |
| Solids, total suspended | single grab sample | ≤ 60 mg/L | all year |
| Solids, total suspended | daily average | ≤ 16 lb/d | all year |
| Flow, in conduit or thru treatment plant | daily average | ≤ .124 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Chlorine, total residual | monthly minimum | ≥ 1 mg/L | all year |
| Chlorine, total residual | monthly maximum | ≤ 4 mg/L | all year |
| E. coli | daily average | ≤ 126 CFU/100mL | all year |
| E. coli | single grab sample | ≤ 399 CFU/100mL | all year |
Cited limits by parameter: Texas's rules and the federal ones.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/TX0053503 · MCP: https://passage-data.com/mcp