Sewage treatment plant, Austwell, Texas. NPDES permit TX0048038 expired Dec 8, 2025; its limits still apply. Last 12 months: over a limit 3 times (last June 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| May 2026 | Solids, total suspended, daily average | 20.05 mg/L | ≤ 20 mg/L | 0% |
| June 2026 | Enterococci, daily average | 122.2 CFU/100mL | ≤ 35 CFU/100mL | 249% |
| June 2026 | Enterococci, single grab sample | 122.2 CFU/100mL | ≤ 104 CFU/100mL | 18% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Oxygen, dissolved [DO] | monthly minimum | ≥ 2 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 20 mg/L | all year |
| BOD, 5-day, 20 deg. C | single grab sample | ≤ 65 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 10 lb/d | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, total suspended | daily average | ≤ 20 mg/L | all year |
| Solids, total suspended | single grab sample | ≤ 65 mg/L | all year |
| Solids, total suspended | daily average | ≤ 10 lb/d | all year |
| Chlorine, total residual | monthly minimum | ≥ 1 mg/L | all year |
| Chlorine, total residual | monthly maximum | ≤ 4 mg/L | all year |
| Enterococci | daily average | ≤ 35 CFU/100mL | all year |
| Enterococci | single grab sample | ≤ 104 CFU/100mL | all year |
Cited limits by parameter: Texas's rules and the federal ones.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/TX0048038 · MCP: https://passage-data.com/mcp