Passage Data · Check a report · Use it from your AI
Sewage treatment plant, major discharger, Denison, Texas. NPDES permit TX0047228, in force until Sep 24, 2031. Last 12 months: no values over a limit, 2 of 17 reports late. Source: EPA ECHO, Oct 22, 2026.
| Parameter | Statistic | Limit | Months | Outfall |
|---|---|---|---|---|
| Oxygen, dissolved [DO] | monthly minimum | ≥ 2 mg/L | all year | 001 |
| BOD, 5-day, 20 deg. C | daily average | ≤ 20 mg/L | all year | 001 |
| BOD, 5-day, 20 deg. C | daily maximum | ≤ 45 mg/L | all year | 001 |
| BOD, 5-day, 20 deg. C | daily average | ≤ 1001 lb/d | all year | 001 |
| pH | minimum | ≥ 6 SU | all year | 001 |
| pH | maximum | ≤ 9 SU | all year | 001 |
| Solids, total suspended | daily average | ≤ 20 mg/L | all year | 001 |
| Solids, total suspended | daily maximum | ≤ 45 mg/L | all year | 001 |
| Solids, total suspended | daily average | ≤ 1001 lb/d | all year | 001 |
| Flow, in conduit or thru treatment plant | daily average | report only (MGD) | all year | 001 |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year | 001 |
| Flow, in conduit or thru treatment plant | 2-hour peak | ≤ 9028 gal/min | all year | 001 |
| Flow, in conduit or thru treatment plant | annual average | ≤ 6 MGD | all year | 001 |
| E. coli | daily average | ≤ 126 CFU/100mL | all year | 001 |
| E. coli | daily maximum | ≤ 399 CFU/100mL | all year | 001 |
| Whole effluent toxicity - retest #2 | 48-hour minimum | report only (pass=0;fail=1) | all year | TX1 |
| Whole effluent toxicity - retest #2 | monthly average minimum | report only (pass=0;fail=1) | all year | TX1 |
| IC25 Low Flow Pass/Fail Static Renewal 48Hr Acute Daphnia pulex | 48-hour minimum | report only (pass=0;fail=1) | all year | TX1 |
| IC25 Low Flow Pass/Fail Static Renewal 48Hr Acute Daphnia pulex | monthly average minimum | report only (pass=0;fail=1) | all year | TX1 |
| IC25 Low Flow Pass/Fail Static Renewal 48Hr Acute Pimephales promelas | 48-hour minimum | report only (pass=0;fail=1) | all year | TX1 |
| IC25 Low Flow Pass/Fail Static Renewal 48Hr Acute Pimephales promelas | monthly average minimum | report only (pass=0;fail=1) | all year | TX1 |
| IC25 Lethal Static Renewal 48HR Acute Daphnia pulex | 48-hour minimum | report only (%) | all year | TX1 |
| IC25 Lethal Static Renewal 48HR Acute Daphnia pulex | monthly average minimum | report only (%) | all year | TX1 |
| IC25 Lethal Static Renewal 48HR Acute Pimephales promelas | 48-hour minimum | report only (%) | all year | TX1 |
| IC25 Lethal Static Renewal 48HR Acute Pimephales promelas | monthly average minimum | report only (%) | all year | TX1 |
| LC50 Pass/Fail Static 24Hr Acute D. Pulex | single sample | report only (pass=0;fail=1) | all year | TXA |
| LC50 Pass/Fail Static 24Hr Acute Pimephales promelas | single sample | report only (pass=0;fail=1) | all year | TXA |
Cited limits by parameter: Texas's rules and the federal ones.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/TX0047228 · MCP: https://passage-data.com/mcp