Passage Data · Check a report · Use it from your AI
Sewage treatment plant, major discharger, Corpus Christi, Texas. NPDES permit TX0047082 expired Mar 3, 2025; its limits still apply. Last 12 months: over a limit 3 times (last August 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| November 2025 | Nitrogen, ammonia total [as N], daily maximum | 24.9 mg/L | ≤ 24 mg/L | 4% |
| March 2026 | Enterococci, daily maximum | 551.4 MPN/100mL | ≤ 104 MPN/100mL | 430% |
| August 2026 | Enterococci, daily maximum | 2419.6 MPN/100mL | ≤ 104 MPN/100mL | 2227% |
| Parameter | Statistic | Limit | Months | Outfall |
|---|---|---|---|---|
| Oxygen, dissolved [DO] | monthly minimum | ≥ 4 mg/L | all year | 001 |
| BOD, 5-day, 20 deg. C | daily average | ≤ 20 mg/L | all year | 001 |
| BOD, 5-day, 20 deg. C | daily maximum | ≤ 45 mg/L | all year | 001 |
| BOD, 5-day, 20 deg. C | daily average | ≤ 834 lb/d | all year | 001 |
| pH | minimum | ≥ 6 SU | all year | 001 |
| pH | maximum | ≤ 9 SU | all year | 001 |
| Solids, total suspended | daily average | ≤ 20 mg/L | all year | 001 |
| Solids, total suspended | daily maximum | ≤ 45 mg/L | all year | 001 |
| Solids, total suspended | daily average | ≤ 834 lb/d | all year | 001 |
| Nitrogen, ammonia total [as N] | daily average | ≤ 12 mg/L | all year | 001 |
| Nitrogen, ammonia total [as N] | daily maximum | ≤ 24 mg/L | all year | 001 |
| Nitrogen, ammonia total [as N] | daily average | ≤ 500 lb/d | all year | 001 |
| Zinc, total [as Zn] | daily average | report only (mg/L) | all year | 001 |
| Zinc, total [as Zn] | daily maximum | report only (mg/L) | all year | 001 |
| Zinc, total [as Zn] | daily average | report only (lb/d) | all year | 001 |
| Flow, in conduit or thru treatment plant | daily average | report only (MGD) | all year | 001 |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year | 001 |
| Flow, in conduit or thru treatment plant | 2-hour peak | ≤ 10416 gal/min | all year | 001 |
| Flow, in conduit or thru treatment plant | annual average | ≤ 5 MGD | all year | 001 |
| Chlorine, total residual | instantaneous maximum | < .1 mg/L | all year | 001 |
| Chlorine, total residual | monthly minimum | ≥ 1 mg/L | all year | 001 |
| Enterococci | daily average | ≤ 35 MPN/100mL | all year | 001 |
| Enterococci | daily maximum | ≤ 104 MPN/100mL | all year | 001 |
| Whole effluent toxicity - retest #1 | 7-day minimum | report only (pass=0;fail=1) | all year | TX1 |
| Whole effluent toxicity - retest #1 | 7-day minimum | report only (pass=0;fail=1) | all year | TX1 |
| Whole effluent toxicity - retest #1 | monthly average minimum | report only (pass=0;fail=1) | all year | TX1 |
| Whole effluent toxicity - retest #1 | monthly average minimum | report only (pass=0;fail=1) | all year | TX1 |
| Whole effluent toxicity - retest #2 | 7-day minimum | report only (pass=0;fail=1) | all year | TX1 |
| Whole effluent toxicity - retest #2 | 7-day minimum | report only (pass=0;fail=1) | all year | TX1 |
| Whole effluent toxicity - retest #2 | monthly average minimum | report only (pass=0;fail=1) | all year | TX1 |
| Whole effluent toxicity - retest #2 | monthly average minimum | report only (pass=0;fail=1) | all year | TX1 |
| IC25 Low Flow Pass/Fail Lethal Static Renewal 7 Day Chronic Americamysis bahia (Mysidopsis bahia) | 7-day minimum | report only (pass=0;fail=1) | all year | TX1 |
| IC25 Low Flow Pass/Fail Lethal Static Renewal 7 Day Chronic Americamysis bahia (Mysidopsis bahia) | monthly average minimum | report only (pass=0;fail=1) | all year | TX1 |
| IC25 Low Flow Pass/Fail Lethal Static Renewal 7 Day Chronic Menidia beryllina | 7-day minimum | report only (pass=0;fail=1) | all year | TX1 |
| IC25 Low Flow Pass/Fail Lethal Static Renewal 7 Day Chronic Menidia beryllina | monthly average minimum | report only (pass=0;fail=1) | all year | TX1 |
| IC25 Low Flow Pass/Fail Sub-Lethal Static Renewal 7 Day Chronic Americamysis bahia (M. bahia) | 7-day minimum | report only (pass=0;fail=1) | all year | TX1 |
| IC25 Low Flow Pass/Fail Sub-Lethal Static Renewal 7 Day Chronic Americamysis bahia (M. bahia) | monthly average minimum | report only (pass=0;fail=1) | all year | TX1 |
| IC25 Low Flow Pass/Fail Sub-Lethal Static Renewal 7 Day Chronic Menidia beryllina | 7-day minimum | report only (pass=0;fail=1) | all year | TX1 |
| IC25 Low Flow Pass/Fail Sub-Lethal Static Renewal 7 Day Chronic Menidia beryllina | monthly average minimum | report only (pass=0;fail=1) | all year | TX1 |
| IC25 Lethal Static Renewal 7 Day Chronic Americamysis bahia (formerly Mysidopsis bahia) | 7-day minimum | report only (%) | all year | TX1 |
| IC25 Lethal Static Renewal 7 Day Chronic Americamysis bahia (formerly Mysidopsis bahia) | monthly average minimum | report only (%) | all year | TX1 |
| IC25 Lethal Static Renewal 7 Day Chronic Menidia beryllina | 7-day minimum | report only (%) | all year | TX1 |
| IC25 Lethal Static Renewal 7 Day Chronic Menidia beryllina | monthly average minimum | report only (%) | all year | TX1 |
| IC25 Sub-Lethal Static Renewal 7 Day Chronic Americamysis bahia (formerly Mysidopsis bahia) | 7-day minimum | report only (%) | all year | TX1 |
| IC25 Sub-Lethal Static Renewal 7 Day Chronic Americamysis bahia (formerly Mysidopsis bahia) | monthly average minimum | report only (%) | all year | TX1 |
| IC25 Sub-Lethal Static Renewal 7 Day Chronic Menidia beryllina | 7-day minimum | report only (%) | all year | TX1 |
| IC25 Sub-Lethal Static Renewal 7 Day Chronic Menidia beryllina | monthly average minimum | report only (%) | all year | TX1 |
| Whole effluent toxicity - retest #1 | single sample | report only (pass=0;fail=1) | all year | TXA |
| Whole effluent toxicity - retest #2 | single sample | report only (pass=0;fail=1) | all year | TXA |
| LC50 Pass/Fail Static 24Hr Acute Americamysis bahia (formerly Mysidopsis bahia) | single sample | report only (pass=0;fail=1) | all year | TXA |
| LC50 Pass/Fail Static 24Hr Acute Menidia menidia | single sample | report only (pass=0;fail=1) | all year | TXA |
Cited limits by parameter: Texas's rules and the federal ones.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/TX0047082 · MCP: https://passage-data.com/mcp