Passage Data · Check a report · Use it from your AI
Sewage treatment plant, Teague, Texas. NPDES permit TX0034495, in force until Sep 2, 2027. Last 12 months: over a limit 25 times (last August 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| October 2025 | pH, maximum | 9.8 SU | ≤ 9 SU | — |
| November 2025 | E. coli, daily average | 136.93 CFU/100mL | ≤ 126 CFU/100mL | 9% |
| November 2025 | pH, maximum | 9.1 SU | ≤ 9 SU | — |
| December 2025 | BOD, 5-day, 20 deg. C, daily average | 34.6 mg/L | ≤ 30 mg/L | 15% |
| December 2025 | E. coli, daily average | 2727.66 CFU/100mL | ≤ 126 CFU/100mL | 2065% |
| December 2025 | E. coli, single grab sample | 4839 CFU/100mL | ≤ 399 CFU/100mL | 1113% |
| January 2026 | E. coli, daily average | 222.48 CFU/100mL | ≤ 126 CFU/100mL | 77% |
| January 2026 | E. coli, single grab sample | 1120 CFU/100mL | ≤ 399 CFU/100mL | 181% |
| February 2026 | BOD, 5-day, 20 deg. C, daily average | 34.75 mg/L | ≤ 30 mg/L | 16% |
| February 2026 | E. coli, daily average | 1408.49 CFU/100mL | ≤ 126 CFU/100mL | 1018% |
| February 2026 | E. coli, single grab sample | 2600 CFU/100mL | ≤ 399 CFU/100mL | 552% |
| March 2026 | BOD, 5-day, 20 deg. C, daily average | 46.6 mg/L | ≤ 30 mg/L | 55% |
| March 2026 | E. coli, single grab sample | 4840 CFU/100mL | ≤ 399 CFU/100mL | 1113% |
| April 2026 | BOD, 5-day, 20 deg. C, daily average | 31 mg/L | ≤ 30 mg/L | 3% |
| April 2026 | E. coli, daily average | 1281.5 CFU/100mL | ≤ 126 CFU/100mL | 917% |
| April 2026 | E. coli, single grab sample | 4840 CFU/100mL | ≤ 399 CFU/100mL | 1113% |
| April 2026 | pH, maximum | 9.1 SU | ≤ 9 SU | — |
| May 2026 | E. coli, daily average | 1650.68 CFU/100mL | ≤ 126 CFU/100mL | 1210% |
| May 2026 | E. coli, single grab sample | 4840 CFU/100mL | ≤ 399 CFU/100mL | 1113% |
| June 2026 | E. coli, daily average | 302.21 CFU/100mL | ≤ 126 CFU/100mL | 140% |
| June 2026 | E. coli, single grab sample | 1100 CFU/100mL | ≤ 399 CFU/100mL | 176% |
| July 2026 | E. coli, daily average | 2394.91 CFU/100mL | ≤ 126 CFU/100mL | 1801% |
| July 2026 | E. coli, single grab sample | 3970 CFU/100mL | ≤ 399 CFU/100mL | 895% |
| July 2026 | pH, maximum | 9.7 SU | ≤ 9 SU | — |
| August 2026 | pH, maximum | 9.6 SU | ≤ 9 SU | — |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Oxygen, dissolved [DO] | monthly minimum | ≥ 4 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 30 mg/L | all year |
| BOD, 5-day, 20 deg. C | single grab sample | ≤ 100 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 75 lb/d | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, total suspended | daily average | ≤ 90 mg/L | all year |
| Solids, total suspended | daily average | ≤ 225 lb/d | all year |
| Flow, in conduit or thru treatment plant | daily average | ≤ .3 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| E. coli | daily average | ≤ 126 CFU/100mL | all year |
| E. coli | single grab sample | ≤ 399 CFU/100mL | all year |
Cited limits by parameter: Texas's rules and the federal ones.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/TX0034495 · MCP: https://passage-data.com/mcp