Passage Data · Check a report · Use it from your AI

Beechwood Water Supply Corporation

Sewerage Systems, Hemphill, Texas. NPDES permit TX0031267 expired Jul 6, 2026; its limits still apply. Last 12 months: over a limit 10 times (last July 2026), 9 of 14 reports late. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 20 days after each period: form A monthly (13 values), form Q quarterly
Last report on file
July 2026
Oct 2024 – Sep 2025
16 values over a limit, 17 required values missing, 9 of 16 reports late

Last 12 months (Oct 1, 2025 – Sep 30, 2026)

Period endingParameterReportedLimitOver by
October 2025pH, maximum9.08 SU≤ 9 SU—
November 2025BOD, 5-day, 20 deg. C, daily average12.8 mg/L≤ 10 mg/L28%
November 2025Chlorine, total residual, monthly maximum4.2 mg/L≤ 4 mg/L5%
December 2025BOD, 5-day, 20 deg. C, daily average44 mg/L≤ 10 mg/L340%
December 2025BOD, 5-day, 20 deg. C, single grab sample77 mg/L≤ 35 mg/L120%
January 2026BOD, 5-day, 20 deg. C, daily average18.6 mg/L≤ 10 mg/L86%
February 2026BOD, 5-day, 20 deg. C, daily average44 mg/L≤ 10 mg/L340%
March 2026BOD, 5-day, 20 deg. C, daily average18.6 mg/L≤ 10 mg/L86%
July 2026BOD, 5-day, 20 deg. C, daily average7.17 lb/d≤ 4.2 lb/d71%
July 2026Solids, total suspended, daily average15.1 lb/d≤ 6.3 lb/d140%

Limits in force (15)

ParameterStatisticLimitMonths
Oxygen, dissolved [DO]monthly minimum≥ 4 mg/Lall year
BOD, 5-day, 20 deg. Cdaily average≤ 10 mg/Lall year
BOD, 5-day, 20 deg. Csingle grab sample≤ 35 mg/Lall year
BOD, 5-day, 20 deg. Cdaily average≤ 4.2 lb/dall year
pHminimum≥ 6 SUall year
pHmaximum≤ 9 SUall year
Solids, total suspendeddaily average≤ 15 mg/Lall year
Solids, total suspendedsingle grab sample≤ 60 mg/Lall year
Solids, total suspendeddaily average≤ 6.3 lb/dall year
Flow, in conduit or thru treatment plantdaily average≤ .05 MGDall year
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year
Chlorine, total residualmonthly minimum≥ 1 mg/Lall year
Chlorine, total residualmonthly maximum≤ 4 mg/Lall year
E. colidaily average≤ 126 CFU/100mLall year
E. colisingle grab sample≤ 399 CFU/100mLall year

How strict are these limits?

Cited limits by parameter: Texas's rules and the federal ones.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/TX0031267 · MCP: https://passage-data.com/mcp