Passage Data · Check a report · Use it from your AI

Eustace, City of

Sewage treatment plant, Eustace, Texas. NPDES permit TX0027481, in force until Feb 13, 2028. Last 12 months: over a limit 11 times (last July 2026), 1 of 11 reports late. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 20 days after each period: form A monthly (15 values)
Renewal application due
Aug 17, 2027 · 180 days before expiry; your permit may set another date
Last report on file
August 2026
Oct 2024 – Sep 2025
16 values over a limit, 0 required values missing, 1 of 12 reports late

Last 12 months (Oct 1, 2025 – Sep 30, 2026)

Period endingParameterReportedLimitOver by
December 2025E. coli, daily average888 CFU/100mL≤ 126 CFU/100mL605%
December 2025E. coli, single grab sample2420 CFU/100mL≤ 399 CFU/100mL507%
January 2026BOD, 5-day, 20 deg. C, daily average14.3 mg/L≤ 10 mg/L43%
January 2026E. coli, single grab sample2420 CFU/100mL≤ 399 CFU/100mL507%
January 2026Solids, total suspended, daily average37.2 mg/L≤ 15 mg/L148%
January 2026Solids, total suspended, single grab sample64 mg/L≤ 60 mg/L7%
March 2026Solids, total suspended, daily average15.2 mg/L≤ 15 mg/L1%
April 2026BOD, 5-day, 20 deg. C, daily average17.7 lb/d≤ 10 lb/d77%
April 2026Solids, total suspended, daily average19.4 mg/L≤ 15 mg/L29%
April 2026Solids, total suspended, daily average68.3 lb/d≤ 16 lb/d327%
July 2026Flow, in conduit or thru treatment plant, daily average.37 MGD≤ .125 MGD196%

Limits in force (15)

ParameterStatisticLimitMonths
Oxygen, dissolved [DO]monthly minimum≥ 4 mg/Lall year
BOD, 5-day, 20 deg. Cdaily average≤ 10 mg/Lall year
BOD, 5-day, 20 deg. Csingle grab sample≤ 35 mg/Lall year
BOD, 5-day, 20 deg. Cdaily average≤ 10 lb/dall year
pHminimum≥ 6 SUall year
pHmaximum≤ 9 SUall year
Solids, total suspendeddaily average≤ 15 mg/Lall year
Solids, total suspendedsingle grab sample≤ 60 mg/Lall year
Solids, total suspendeddaily average≤ 16 lb/dall year
Flow, in conduit or thru treatment plantdaily average≤ .125 MGDall year
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year
Chlorine, total residualmonthly minimum≥ 1 mg/Lall year
Chlorine, total residualmonthly maximum≤ 4 mg/Lall year
E. colidaily average≤ 126 CFU/100mLall year
E. colisingle grab sample≤ 399 CFU/100mLall year

How strict are these limits?

Cited limits by parameter: Texas's rules and the federal ones.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/TX0027481 · MCP: https://passage-data.com/mcp