Passage Data · Check a report · Use it from your AI
Sewage treatment plant, major discharger, Lake Jackson, Texas. NPDES permit TX0025798, in force until Sep 8, 2030. Last 12 months: over a limit once (last May 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| May 2026 | Enterococci, daily maximum | 2400 CFU/100mL | ≤ 104 CFU/100mL | 2208% |
| Parameter | Statistic | Limit | Months | Outfall |
|---|---|---|---|---|
| Oxygen, dissolved [DO] | monthly minimum | ≥ 2 mg/L | all year | 001 |
| BOD, 5-day, 20 deg. C | daily average | ≤ 20 mg/L | all year | 001 |
| BOD, 5-day, 20 deg. C | daily maximum | ≤ 45 mg/L | all year | 001 |
| BOD, 5-day, 20 deg. C | daily average | ≤ 976 lb/d | all year | 001 |
| pH | minimum | ≥ 6.5 SU | all year | 001 |
| pH | maximum | ≤ 9 SU | all year | 001 |
| Solids, total suspended | daily average | ≤ 20 mg/L | all year | 001 |
| Solids, total suspended | daily maximum | ≤ 45 mg/L | all year | 001 |
| Solids, total suspended | daily average | ≤ 976 lb/d | all year | 001 |
| Copper, total [as Cu] | daily average | report only (mg/L) | all year | 001 |
| Copper, total [as Cu] | daily maximum | report only (mg/L) | all year | 001 |
| Copper, total [as Cu] | daily average | report only (lb/d) | all year | 001 |
| Flow, in conduit or thru treatment plant | daily average | report only (MGD) | all year | 001 |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year | 001 |
| Flow, in conduit or thru treatment plant | 2-hour peak | ≤ 13403 gal/min | all year | 001 |
| Flow, in conduit or thru treatment plant | annual average | ≤ 5.85 MGD | all year | 001 |
| Chlorine, total residual | instantaneous maximum | < .1 mg/L | all year | 001 |
| Chlorine, total residual | monthly minimum | ≥ 1 mg/L | all year | 001 |
| Enterococci | daily average | ≤ 35 CFU/100mL | all year | 001 |
| Enterococci | daily maximum | ≤ 104 CFU/100mL | all year | 001 |
| Whole effluent toxicity - retest #1 | single sample | report only (pass=0;fail=1) | all year | TXA |
| Whole effluent toxicity - retest #2 | single sample | report only (pass=0;fail=1) | all year | TXA |
| LC50 Pass/Fail Static 24Hr Acute Americamysis bahia (formerly Mysidopsis bahia) | single sample | report only (pass=0;fail=1) | all year | TXA |
| LC50 Pass/Fail Static 24Hr Acute Menidia beryllina | single sample | report only (pass=0;fail=1) | all year | TXA |
Cited limits by parameter: Texas's rules and the federal ones.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/TX0025798 · MCP: https://passage-data.com/mcp