Passage Data · Check a report · Use it from your AI
Sewage treatment plant, Ector, Texas. NPDES permit TX0025151, in force until Jun 15, 2031. Last 12 months: over a limit 4 times (last August 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| January 2026 | E. coli, daily average | 1010 CFU/100mL | ≤ 126 CFU/100mL | 702% |
| January 2026 | E. coli, single grab sample | 1010 CFU/100mL | ≤ 399 CFU/100mL | 153% |
| June 2026 | Flow, in conduit or thru treatment plant, daily average | .104 MGD | ≤ .099 MGD | 5% |
| August 2026 | pH, maximum | 9.51 SU | ≤ 9 SU | — |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Oxygen, dissolved [DO] | monthly minimum | ≥ 4 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 30 mg/L | all year |
| BOD, 5-day, 20 deg. C | single grab sample | ≤ 100 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 25 lb/d | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, total suspended | daily average | ≤ 90 mg/L | all year |
| Solids, total suspended | daily average | ≤ 74 lb/d | all year |
| Flow, in conduit or thru treatment plant | daily average | ≤ .099 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Chlorine, total residual | monthly minimum | ≥ 1 mg/L | all year |
| Chlorine, total residual | monthly maximum | ≤ 4 mg/L | all year |
| E. coli | daily average | ≤ 126 CFU/100mL | all year |
| E. coli | single grab sample | ≤ 399 CFU/100mL | all year |
Cited limits by parameter: Texas's rules and the federal ones.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/TX0025151 · MCP: https://passage-data.com/mcp