Passage Data · Check a report · Use it from your AI
Sewage treatment plant, Rosebud, Texas. NPDES permit TX0023981, in force until Nov 8, 2029. Last 12 months: over a limit 11 times (last September 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| January 2026 | E. coli, single grab sample | 1986 CFU/100mL | ≤ 399 CFU/100mL | 398% |
| March 2026 | E. coli, daily average | 2420 CFU/100mL | ≤ 126 CFU/100mL | 1821% |
| March 2026 | E. coli, single grab sample | 2420 CFU/100mL | ≤ 399 CFU/100mL | 507% |
| March 2026 | Solids, total suspended, daily average | 16.75 mg/L | ≤ 15 mg/L | 12% |
| April 2026 | Solids, total suspended, daily average | 24 mg/L | ≤ 15 mg/L | 60% |
| May 2026 | Solids, total suspended, daily average | 21.5 mg/L | ≤ 15 mg/L | 43% |
| May 2026 | Solids, total suspended, single grab sample | 64 mg/L | ≤ 60 mg/L | 7% |
| June 2026 | E. coli, daily average | 645.17 CFU/100mL | ≤ 126 CFU/100mL | 412% |
| June 2026 | E. coli, single grab sample | 2420 CFU/100mL | ≤ 399 CFU/100mL | 507% |
| July 2026 | E. coli, single grab sample | 1550 CFU/100mL | ≤ 399 CFU/100mL | 288% |
| September 2026 | Chlorine, total residual, monthly minimum | .9 mg/L | ≥ 1 mg/L | 10% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Oxygen, dissolved [DO] | monthly minimum | ≥ 4 mg/L | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, total suspended | daily average | ≤ 15 mg/L | all year |
| Solids, total suspended | single grab sample | ≤ 60 mg/L | all year |
| Solids, total suspended | daily average | ≤ 31 lb/d | all year |
| Nitrogen, ammonia total [as N] | daily average | ≤ 3 mg/L | all year |
| Nitrogen, ammonia total [as N] | single grab sample | ≤ 15 mg/L | all year |
| Nitrogen, ammonia total [as N] | daily average | ≤ 6 lb/d | all year |
| Flow, in conduit or thru treatment plant | daily average | ≤ .25 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Chlorine, total residual | monthly minimum | ≥ 1 mg/L | all year |
| Chlorine, total residual | monthly maximum | ≤ 4 mg/L | all year |
| E. coli | daily average | ≤ 126 CFU/100mL | all year |
| E. coli | single grab sample | ≤ 399 CFU/100mL | all year |
| BOD, carbonaceous [5 day, 20 C] | daily average | ≤ 10 mg/L | all year |
| BOD, carbonaceous [5 day, 20 C] | single grab sample | ≤ 35 mg/L | all year |
| BOD, carbonaceous [5 day, 20 C] | daily average | ≤ 21 lb/d | all year |
Cited limits by parameter: Texas's rules and the federal ones.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/TX0023981 · MCP: https://passage-data.com/mcp