Passage Data · Check a report · Use it from your AI
Sewage treatment plant, major discharger, Wharton, Texas. NPDES permit TX0021288, in force until Apr 17, 2030. Last 12 months: over a limit once (last April 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| April 2026 | E. coli, daily maximum | 2419.6 MPN/100mL | ≤ 399 CFU/100mL | 506% |
| Parameter | Statistic | Limit | Months | Outfall |
|---|---|---|---|---|
| Oxygen, dissolved [DO] | monthly minimum | ≥ 3 mg/L | all year | 001 |
| BOD, 5-day, 20 deg. C | daily average | ≤ 20 mg/L | all year | 001 |
| BOD, 5-day, 20 deg. C | daily maximum | ≤ 45 mg/L | all year | 001 |
| BOD, 5-day, 20 deg. C | daily average | ≤ 250 lb/d | all year | 001 |
| pH | minimum | ≥ 6 SU | all year | 001 |
| pH | maximum | ≤ 9 SU | all year | 001 |
| Solids, total suspended | daily average | ≤ 20 mg/L | all year | 001 |
| Solids, total suspended | daily maximum | ≤ 45 mg/L | all year | 001 |
| Solids, total suspended | daily average | ≤ 250 lb/d | all year | 001 |
| Flow, in conduit or thru treatment plant | daily average | report only (MGD) | all year | 001 |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year | 001 |
| Flow, in conduit or thru treatment plant | 2-hour peak | ≤ 2827 gal/min | all year | 001 |
| Flow, in conduit or thru treatment plant | annual average | ≤ 1.5 MGD | all year | 001 |
| Chlorine, total residual | instantaneous maximum | < .1 mg/L | all year | 001 |
| Chlorine, total residual | monthly minimum | ≥ 1 mg/L | all year | 001 |
| E. coli | daily average | ≤ 126 CFU/100mL | all year | 001 |
| E. coli | daily maximum | ≤ 399 CFU/100mL | all year | 001 |
| Low Flow Pass/Fail Static Renewal 48Hr Acute Daphnia pulex | 48-hour minimum | report only (pass=0;fail=1) | all year | TX1 |
| Low Flow Pass/Fail Static Renewal 48Hr Acute Daphnia pulex | monthly average minimum | report only (pass=0;fail=1) | all year | TX1 |
| NOAEC Lethal Statis Renewal 48 Hr Acute Daphnia pulex | 48-hour minimum | report only (%) | all year | TX1 |
| NOAEC Lethal Statis Renewal 48 Hr Acute Daphnia pulex | monthly average minimum | report only (%) | all year | TX1 |
| LOAEC Lethal Static Renewal 48HR Acute Daphnia pulex | 48-hour minimum | report only (%) | all year | TX1 |
| LOAEC Lethal Static Renewal 48HR Acute Daphnia pulex | monthly average minimum | report only (%) | all year | TX1 |
| Whole effluent toxicity - retest #1 | single sample | report only (pass=0;fail=1) | all year | TXA |
| Whole effluent toxicity - retest #2 | single sample | report only (pass=0;fail=1) | all year | TXA |
| LC50 Pass/Fail Static 24Hr Acute D. Pulex | single sample | report only (pass=0;fail=1) | all year | TXA |
| LC50 Pass/Fail Static 24Hr Acute Pimephales promelas | single sample | report only (pass=0;fail=1) | all year | TXA |
Cited limits by parameter: Texas's rules and the federal ones.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/TX0021288 · MCP: https://passage-data.com/mcp