Passage Data · Check a report · Use it from your AI

Junction, City of

Sewage treatment plant, Junction, Texas. NPDES permit TX0021075, in force until Feb 3, 2027. Last 12 months: no values over a limit. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 20 days after each period: outfall 001 form A monthly (17 values), outfall 101 form A monthly (1 value)
Renewal application due
Aug 7, 2026 · 180 days before expiry; your permit may set another date
Last report on file
September 2026
Oct 2024 – Sep 2025
1 value over a limit, 0 required values missing, 4 of 24 reports late

Limits in force (18)

ParameterStatisticLimitMonthsOutfall
Oxygen, dissolved [DO]monthly minimum≥ 4 mg/Lall year001
BOD, 5-day, 20 deg. Cdaily average≤ 30 mg/Lall year001
BOD, 5-day, 20 deg. Csingle grab sample≤ 100 mg/Lall year001
BOD, 5-day, 20 deg. Cdaily average≤ 70 lb/dall year001
pHminimum≥ 6 SUall year001
pHmaximum≤ 9 SUall year001
Solids, total suspendeddaily average≤ 90 mg/Lall year001
Solids, total suspendeddaily average≤ 210 lb/dall year001
Phosphorus, total [as P]daily averagereport only (mg/L)all year001
Phosphorus, total [as P]single grab samplereport only (mg/L)all year001
Phosphorus, total [as P]daily averagereport only (lb/d)all year001
Flow, in conduit or thru treatment plantdaily average≤ .28 MGDall year001
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year001
Chlorine, total residualmonthly minimum≥ 1 mg/Lall year001
Chlorine, total residualmonthly maximum≤ 4 mg/Lall year001
E. colidaily average≤ 126 CFU/100mLall year001
E. colisingle grab sample≤ 399 CFU/100mLall year001
Flow, in conduit or thru treatment plantdaily averagereport only (MGD)all year101

How strict are these limits?

Cited limits by parameter: Texas's rules and the federal ones.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/TX0021075 · MCP: https://passage-data.com/mcp