NPDES permit TX0003239 · Minor NON-POTW · effective, expires 2029-07-23 · EPA's file as of 2026-09-19
Check this month's numbers before you fileLast period with anything received: 2026-07-31. Most often over: Copper, total [as Cu] (5), E. coli (2).
Reports are due about 25 days after each monitoring period ends (read off this permit's own late-day counts in EPA's filings).
| Outfall | Parameter | Statistic | Limit | Months |
|---|---|---|---|---|
| 001 | Temperature, water deg. fahrenheit | DAILY AV | <= 100 deg F | all year |
| 001 | Temperature, water deg. fahrenheit | DAILY MX | <= 105 deg F | all year |
| 001 | BOD, 5-day, 20 deg. C | DAILY AV | <= 20 mg/L | all year |
| 001 | BOD, 5-day, 20 deg. C | DAILY MX | <= 45 mg/L | all year |
| 001 | Oxygen demand, chem. [high level] [COD] | DAILY AV | <= 290 lb/d | all year |
| 001 | Oxygen demand, chem. [high level] [COD] | DAILY MX | <= 437 lb/d | all year |
| 001 | pH | MINIMUM | >= 6 SU | all year |
| 001 | pH | MAXIMUM | <= 9 SU | all year |
| 001 | Solids, total suspended | DAILY AV | <= 75 lb/d | all year |
| 001 | Solids, total suspended | DAILY MX | <= 150 lb/d | all year |
| 001 | Oil & Grease | DAILY AV | <= 14 lb/d | all year |
| 001 | Oil & Grease | DAILY MX | <= 28 lb/d | all year |
| 001 | Copper, total [as Cu] | DAILY AV | <= .0403 mg/L | all year |
| 001 | Copper, total [as Cu] | DAILY MX | <= .0852 mg/L | all year |
| 001 | Copper, total [as Cu] | DAILY AV | <= .029 lb/d | all year |
| 001 | Copper, total [as Cu] | DAILY MX | <= .063 lb/d | all year |
| 001 | Flow, in conduit or thru treatment plant | DAILY AV | <= .43 MGD | all year |
| 001 | Flow, in conduit or thru treatment plant | DAILY MX | <= .85 MGD | all year |
| 001 | E. coli | DAILY AV | <= 126 CFU/100mL | all year |
| 001 | E. coli | DAILY MX | <= 399 CFU/100mL | all year |
| 001 | Mercury, total [as Hg] | DAILY AV | <= .00041 mg/L | all year |
| 001 | Mercury, total [as Hg] | DAILY MX | <= .00086 mg/L | all year |
| 001 | Mercury, total [as Hg] | DAILY AV | <= .00029 lb/d | all year |
| 001 | Mercury, total [as Hg] | DAILY MX | <= .00061 lb/d | all year |
| 101 | Flow, in conduit or thru treatment plant | DAILY AV | report only | all year |
| 101 | Flow, in conduit or thru treatment plant | DAILY MX | report only | all year |
| 101 | Chlorine, total residual | MINIMUM | >= 1 mg/L | all year |
| 101 | Chlorine, total residual | MO MAX | <= 4 mg/L | all year |
Built from EPA's ECHO bulk files. EPA's file, not the permit document, is the source: read your permit. Check a report before you file it · All states