Passage Data · Check a report · Use it from your AI

Luminant Generation Company LL

Electric Services, major discharger, Colorado City, Texas. NPDES permit TX0001171 expired Jul 2, 2025; its limits still apply. Last 12 months: over a limit once (last January 2026). Source: EPA ECHO, Oct 22, 2026.

Reports due
About 25 days after each period: outfall 002 form A monthly (12 values), outfall 102 form A monthly (6 values), outfall 202 form A monthly (6 values), outfall TX2 form Q quarterly (28 values), outfall TXB form S twice a year
Last report on file
August 2026
Oct 2024 – Sep 2025
0 values over a limit, 38 required values missing, 7 of 42 reports late

Last 12 months (Oct 1, 2025 – Sep 30, 2026)

Period endingParameterReportedLimitOver by
January 2026Oil & Grease, daily maximum35.6 mg/L≤ 20 mg/L78%

Limits in force (56)

ParameterStatisticLimitMonthsOutfall
Temperature, water deg. fahrenheitdaily average≤ 115 deg Fall year002
Temperature, water deg. fahrenheitdaily maximum≤ 120 deg Fall year002
pHminimum≥ 6 SUall year002
pHmaximum≤ 9 SUall year002
Flow, in conduit or thru treatment plantdaily average≤ 720 MGDall year002
Flow, in conduit or thru treatment plantdaily maximum≤ 720 MGDall year002
Chlorine, total residualdaily maximum≤ .2 mg/Lall year002
Chlorine, total residualdaily maximum≤ 500 lb/dall year002
Chlorine, free availabledaily average≤ .2 mg/Lall year002
Chlorine, free availabledaily maximum≤ .5 mg/Lall year002
Chlorine, free availabledaily average≤ 100 lb/dall year002
Chlorine, free availabledaily maximum≤ 250 lb/dall year002
Solids, total suspendeddaily average≤ 30 mg/Lall year102
Solids, total suspendeddaily maximum≤ 100 mg/Lall year102
Oil & Greasedaily average≤ 15 mg/Lall year102
Oil & Greasedaily maximum≤ 20 mg/Lall year102
Flow, in conduit or thru treatment plantdaily averagereport only (MGD)all year102
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year102
Copper, total [as Cu]daily average≤ .5 mg/Lall year202
Copper, total [as Cu]daily maximum≤ 1 mg/Lall year202
Iron, total [as Fe]daily average≤ 1 mg/Lall year202
Iron, total [as Fe]daily maximum≤ 1 mg/Lall year202
Flow, in conduit or thru treatment plantdaily averagereport only (MGD)all year202
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year202
Whole effluent toxicity - retest #17-day minimumreport only (pass=0;fail=1)all yearTX2
Whole effluent toxicity - retest #1monthly average minimumreport only (pass=0;fail=1)all yearTX2
Whole effluent toxicity - retest #27-day minimumreport only (pass=0;fail=1)all yearTX2
Whole effluent toxicity - retest #2monthly average minimumreport only (pass=0;fail=1)all yearTX2
Low Flow Pass/Fail Survival Test Static Renewal 7 Day Chronic Ceriodaphnia dubia7-day minimumreport only (pass=0;fail=1)all yearTX2
Low Flow Pass/Fail Survival Test Static Renewal 7 Day Chronic Ceriodaphnia dubiamonthly average minimumreport only (pass=0;fail=1)all yearTX2
Low Flow Pass/Fail Survival Test Static Renewal 7 Day Chronic Pimephales promelas7-day minimumreport only (pass=0;fail=1)all yearTX2
Low Flow Pass/Fail Survival Test Static Renewal 7 Day Chronic Pimephales promelasmonthly average minimumreport only (pass=0;fail=1)all yearTX2
NOEC Lethal Static Renewal 7 Day Chronic Ceriodaphnia dubia7-day minimumreport only (%)all yearTX2
NOEC Lethal Static Renewal 7 Day Chronic Ceriodaphnia dubiamonthly average minimumreport only (%)all yearTX2
NOEC Lethal Static Renewal 7 Day Chronic Pimephales promelas7-day minimumreport only (%)all yearTX2
NOEC Lethal Static Renewal 7 Day Chronic Pimephales promelasmonthly average minimumreport only (%)all yearTX2
NOEC Sub-Lethal Static Renewal 7 Day Chronic Ceriodaphnia dubia7-day averagereport only (%)all yearTX2
NOEC Sub-Lethal Static Renewal 7 Day Chronic Ceriodaphnia dubiamonthly average minimumreport only (%)all yearTX2
NOEC Sub-Lethal Static Renewal 7 Day Chronic Pimephales promelas7-day minimumreport only (%)all yearTX2
NOEC Sub-Lethal Static Renewal 7 Day Chronic Pimephales promelasmonthly average minimumreport only (%)all yearTX2
Pass/Fail Sub-Lethal Static Renewal 7 Day Chronic Ceriodaphnia dubia7-day minimumreport only (pass=0;fail=1)all yearTX2
Pass/Fail Sub-Lethal Static Renewal 7 Day Chronic Ceriodaphnia dubiamonthly average minimumreport only (pass=0;fail=1)all yearTX2
Pass/Fail Sub-Lethal Static Renewal 7 Day Chronic Pinephales promelas7-day minimumreport only (pass=0;fail=1)all yearTX2
Pass/Fail Sub-Lethal Static Renewal 7 Day Chronic Pinephales promelasmonthly average minimumreport only (pass=0;fail=1)all yearTX2
LOEC Lethal Survival Static Renewal 7 Day Chronic Ceriodaphnia dubia7-day minimumreport only (%)all yearTX2
LOEC Lethal Survival Static Renewal 7 Day Chronic Ceriodaphnia dubiamonthly average minimumreport only (%)all yearTX2
LOEC Lethal Survival Static Renewal 7 Day Chronic Pimephales promelas7-day minimumreport only (%)all yearTX2
LOEC Lethal Survival Static Renewal 7 Day Chronic Pimephales promelasmonthly average minimumreport only (%)all yearTX2
LOEC Sub-Lethal Reproduction Static Renewal 7 Day Chronic Ceriodaphnia dubia7-day minimumreport only (%)all yearTX2
LOEC Sub-Lethal Reproduction Static Renewal 7 Day Chronic Ceriodaphnia dubiamonthly average minimumreport only (%)all yearTX2
LOEC Sub-Lethal Reproduction Static Renewal 7 Day Chronic Pimephales promelas7-day minimumreport only (%)all yearTX2
LOEC Sub-Lethal Reproduction Static Renewal 7 Day Chronic Pimephales promelasmonthly average minimumreport only (%)all yearTX2
Whole effluent toxicity - retest #1single samplereport only (pass=0;fail=1)all yearTXB
Whole effluent toxicity - retest #2single samplereport only (pass=0;fail=1)all yearTXB
LC50 Pass/Fail Static 24Hr Acute D. Pulexsingle samplereport only (pass=0;fail=1)all yearTXB
LC50 Pass/Fail Static 24Hr Acute Pimephales promelassingle samplereport only (pass=0;fail=1)all yearTXB

How strict are these limits?

Cited limits by parameter: Texas's rules and the federal ones.

Same industry: the 87 Electric Services permits in Texas.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/TX0001171 · MCP: https://passage-data.com/mcp