Clay Rural Water System - Wynstone

Water Supply, North Sioux City, South Dakota. NPDES permit SD0028011, in force until Mar 31, 2027. Last 12 months: no values over a limit, 4 of 26 reports late. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 28 days after each period: outfall 001 form A monthly (21 values), outfall 001 form B yearly (2 values), outfall 002 form A monthly (12 values)
Renewal application due
Oct 2, 2026 · 180 days before expiry; your permit may set another date
Last report on file
September 2026
Oct 2024 – Sep 2025
0 values over a limit, 2 required values missing, 1 of 28 reports late

Limits in force (35)

ParameterStatisticLimitMonthsOutfall
Temperature, water deg. centigrade30-day averagereport only (deg C)all year001
Temperature, water deg. centigradedaily maximumreport only (deg C)all year001
Flow rate30-day averagereport only (MGD)all year001
Flow ratedaily maximumreport only (MGD)all year001
Conductivity30-day average≤ 5245 umho/cmall year001
Conductivitydaily maximum≤ 9178 umho/cmall year001
pHdaily minimum≥ 6.5 SUall year001
pHdaily maximum≤ 9 SUall year001
Alkalinity, total [as CaCO3]30-day average≤ 1833 mg/Lall year001
Alkalinity, total [as CaCO3]daily maximum≤ 3208 mg/Lall year001
Solids, total suspended30-day averagereport only (mg/L)all year001
Solids, total suspendeddaily maximumreport only (mg/L)all year001
Nitrogen, nitrate total [as N]30-day averagereport only (mg/L)all year001
Nitrogen, nitrate total [as N]daily maximumreport only (mg/L)all year001
Sulfate, total [as SO4]30-day average≤ 2336 mg/Lall year001
Sulfate, total [as SO4]daily maximum≤ 4088 mg/Lall year001
Fluoride, total [as F]daily maximum≤ 5.8 mg/Lall year001
Radium 226, totalrolling average≤ 25 pCi/Lall year001
Radium 226, totaldaily maximum≤ 75 pCi/Lall year001
Floating solids, waste or visible foam-visualdaily maximumreport only (abst=0;prst=1)all year001
Chlorine, total residualdaily maximum≤ .019 mg/Lall year001
Solids, total dissolved30-day average≤ 3254 mg/Lall year001
Solids, total dissolveddaily maximum≤ 5695 mg/Lall year001
Temperature, water deg. centigrade30-day averagereport only (deg C)all year002
Temperature, water deg. centigradedaily maximumreport only (deg C)all year002
Flow rate30-day averagereport only (MGD)all year002
Flow ratedaily maximumreport only (MGD)all year002
pHdaily minimum≥ 6.5 SUall year002
pHdaily maximum≤ 9 SUall year002
Solids, total suspended30-day averagereport only (mg/L)all year002
Solids, total suspendeddaily maximumreport only (mg/L)all year002
Floating solids, waste or visible foam-visualdaily maximumreport only (abst=0;prst=1)all year002
Chlorine, total residualdaily maximum≤ .019 mg/Lall year002
Flow, totalmonthly totalreport only (Mgal)all year002
Duration of dischargemonthly totalreport only (d)all year002

How strict are these limits?

Cited limits by parameter: South Dakota's rules and the federal ones.