Mobile Home Site Operators, West Columbia, South Carolina. NPDES permit SC0033685 expired Oct 31, 2019; its limits still apply. Last 12 months: over a limit 13 times (last August 2026), 1 of 11 reports late. Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| December 2025 | BOD, 5-day, 20 deg. C, daily maximum | 231 | ≤ 36 lb/d | 542% |
| December 2025 | BOD, 5-day, 20 deg. C, monthly average | 230 | ≤ 18 lb/d | 1178% |
| December 2025 | Chlorine, total residual, daily maximum | 3.88 | ≤ .3 lb/d | 1193% |
| December 2025 | Chlorine, total residual, monthly average | .44 | ≤ .3 mg/L | 47% |
| December 2025 | Chlorine, total residual, monthly average | 3.52 | ≤ .18 lb/d | 1856% |
| December 2025 | Solids, total suspended, daily maximum | 153 | ≤ 108 lb/d | 42% |
| December 2025 | Solids, total suspended, monthly average | 146 | ≤ 54 lb/d | 170% |
| February 2026 | BOD, 5-day, 20 deg. C, monthly average | 30 | ≤ 18 lb/d | 67% |
| February 2026 | BOD, 5-day, 20 deg. C, monthly average | 38 | ≤ 30 mg/L | 27% |
| March 2026 | BOD, 5-day, 20 deg. C, monthly average | 21 | ≤ 18 lb/d | 17% |
| June 2026 | E. coli, daily maximum | 727 | ≤ 349 MPN/100mL | 108% |
| August 2026 | E. coli, 30-day geometric mean | 252.1 | ≤ 126 MPN/100mL | 100% |
| August 2026 | E. coli, daily maximum | 2419.6 | ≤ 349 MPN/100mL | 593% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Oxygen, dissolved [DO] | minimum | ≥ 1 mg/L | all year |
| BOD, 5-day, 20 deg. C | monthly average | ≤ 30 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily maximum | ≤ 60 mg/L | all year |
| BOD, 5-day, 20 deg. C | monthly average | ≤ 18 lb/d | all year |
| BOD, 5-day, 20 deg. C | daily maximum | ≤ 36 lb/d | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 8.5 SU | all year |
| Solids, total suspended | monthly average | ≤ 90 mg/L | all year |
| Solids, total suspended | daily maximum | ≤ 180 mg/L | all year |
| Solids, total suspended | monthly average | ≤ 54 lb/d | all year |
| Solids, total suspended | daily maximum | ≤ 108 lb/d | all year |
| Nitrogen, ammonia total [as N] | monthly average | report only (mg/L) | all year |
| Nitrogen, ammonia total [as N] | daily maximum | report only (mg/L) | all year |
| Nitrogen, ammonia total [as N] | monthly average | report only (lb/d) | all year |
| Nitrogen, ammonia total [as N] | daily maximum | report only (lb/d) | all year |
| Phosphorus, total [as P] | monthly average | report only (mg/L) | all year |
| Phosphorus, total [as P] | daily maximum | report only (mg/L) | all year |
| Phosphorus, total [as P] | monthly average | report only (lb/d) | all year |
| Phosphorus, total [as P] | daily maximum | report only (lb/d) | all year |
| Flow, in conduit or thru treatment plant | monthly average | report only (MGD) | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Chlorine, total residual | monthly average | ≤ .3 mg/L | all year |
| Chlorine, total residual | daily maximum | ≤ .5 mg/L | all year |
| Chlorine, total residual | monthly average | ≤ .18 lb/d | all year |
| Chlorine, total residual | daily maximum | ≤ .3 lb/d | all year |
| E. coli | 30-day geometric mean | ≤ 126 MPN/100mL | all year |
| E. coli | daily maximum | ≤ 349 MPN/100mL | all year |
| E. coli | 30-day geometric mean | ≤ 126 MPN/100mL | all year |
| E. coli | daily maximum | ≤ 800 MPN/100mL | all year |
Cited limits by parameter: South Carolina's rules and the federal ones.