Electric Services, major discharger, Moncks Corner, South Carolina. NPDES permit SC0001091 expired May 31, 2019; its limits still apply. Last 12 months: no values over a limit. Source: EPA ECHO, Oct 22, 2026.
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| pH | instantaneous minimum | ≥ 6 SU | all year |
| pH | instantaneous maximum | ≤ 9 SU | all year |
| Solids, total suspended | monthly average | ≤ 19 mg/L | all year |
| Solids, total suspended | instantaneous maximum | ≤ 50 mg/L | all year |
| Oil & Grease | monthly average | ≤ 8 mg/L | all year |
| Oil & Grease | daily maximum | ≤ 13 mg/L | all year |
| Arsenic, total [as As] | monthly average | report only (ug/L) | all year |
| Arsenic, total [as As] | daily maximum | report only (ug/L) | all year |
| Flow, in conduit or thru treatment plant | monthly average | report only (MGD) | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| %Effect Static Renewal 7 Day Chronic Ceriodaphnia dubia | monthly average | report only (%) | all year |
| %Effect Static Renewal 7 Day Chronic Ceriodaphnia dubia | daily maximum | report only (%) | all year |
Cited limits by parameter: South Carolina's rules and the federal ones.
Same industry: the 17 Electric Services permits in South Carolina.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/SC0001091 · MCP: https://passage-data.com/mcp