Passage Data · Check a report · Use it from your AI
Water Supply, Naguabo, Puerto Rico. NPDES permit PR0026905, in force until Sep 30, 2030. Last 12 months: over a limit 16 times (last June 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| October 2025 | Lead, total [as Pb], daily maximum | .64 ug/L | ≤ .5 ug/L | 28% |
| October 2025 | Phosphorus, total [as P], daily maximum | 1300 ug/L | ≤ 160 ug/L | 713% |
| October 2025 | Zinc, total [as Zn], daily maximum | 79.2 ug/L | ≤ 50.16 ug/L | 58% |
| November 2025 | Lead, total [as Pb], daily maximum | 1.49 ug/L | ≤ .5 ug/L | 198% |
| November 2025 | Zinc, total [as Zn], daily maximum | 54 ug/L | ≤ 50.16 ug/L | 8% |
| December 2025 | Zinc, total [as Zn], daily maximum | 79.1 ug/L | ≤ 50.16 ug/L | 58% |
| January 2026 | Lead, total [as Pb], daily maximum | 1.25 ug/L | ≤ .5 ug/L | 150% |
| January 2026 | Phosphorus, total [as P], daily maximum | 4240 ug/L | ≤ 160 ug/L | 2550% |
| February 2026 | Phosphorus, total [as P], daily maximum | 360 ug/L | ≤ 160 ug/L | 125% |
| March 2026 | Lead, total [as Pb], daily maximum | 1.51 ug/L | ≤ .5 ug/L | 202% |
| March 2026 | Phosphorus, total [as P], daily maximum | 5250 ug/L | ≤ 160 ug/L | 3181% |
| May 2026 | Lead, total [as Pb], daily maximum | .83 ug/L | ≤ .5 ug/L | 66% |
| May 2026 | Phosphorus, total [as P], daily maximum | 2670 ug/L | ≤ 160 ug/L | 1569% |
| June 2026 | Lead, total [as Pb], daily maximum | 7.76 ug/L | ≤ .5 ug/L | 1452% |
| June 2026 | Phosphorus, total [as P], daily maximum | 950 ug/L | ≤ 160 ug/L | 494% |
| June 2026 | Temperature, water deg. centigrade, daily maximum | 31.9 deg C | ≤ 30 deg C | 6% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Temperature, water deg. centigrade | daily maximum | ≤ 30 deg C | all year |
| Turbidity | daily maximum | ≤ 50 NTU | all year |
| Oxygen, dissolved [DO] | minimum | ≥ 5 mg/L | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | daily maximum | ≤ 9 SU | all year |
| Solids, settleable | daily maximum | report only (mL/L) | all year |
| Phosphorus, total [as P] | daily maximum | ≤ 160 ug/L | all year |
| Copper, total [as Cu] | daily maximum | ≤ 3 ug/L | all year |
| Copper, total [as Cu] | daily maximum | ≤ 76.56 ug/L | all year |
| Lead, total [as Pb] | daily maximum | ≤ .5 ug/L | all year |
| Zinc, total [as Zn] | daily maximum | ≤ 37.02 ug/L | all year |
| Zinc, total [as Zn] | daily maximum | ≤ 50.16 ug/L | all year |
| Flow, in conduit or thru treatment plant | daily maximum | ≤ .0296 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Chlorine, total residual | daily maximum | ≤ 11 ug/L | all year |
Cited limits by parameter: we hold no rule of Puerto Rico's own; the federal ones.
Same industry: the 108 Water Supply permits in Puerto Rico.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/PR0026905 · MCP: https://passage-data.com/mcp