Passage Data · Check a report · Use it from your AI
Water Supply, Cabo Rojo, Puerto Rico. NPDES permit PR0026875, in force until Apr 30, 2031. Last 12 months: over a limit 13 times (last August 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| May 2026 | Enterococci, 90th percentile | 2189 #/100mL | ≤ 130 #/100mL | 1584% |
| May 2026 | Enterococci, geometric mean | 515 #/100mL | ≤ 35 #/100mL | 1371% |
| June 2026 | Ammonia & ammonium- total, daily maximum | .19 mg/L | ≤ 81 ug/L | 135% |
| June 2026 | Enterococci, 90th percentile | 2420 #/100mL | ≤ 130 #/100mL | 1762% |
| June 2026 | Enterococci, geometric mean | 218 #/100mL | ≤ 35 #/100mL | 523% |
| July 2026 | Ammonia & ammonium- total, daily maximum | .18 mg/L | ≤ 81 ug/L | 122% |
| July 2026 | Enterococci, 90th percentile | 2420 #/100mL | ≤ 130 #/100mL | 1762% |
| July 2026 | Enterococci, geometric mean | 231 #/100mL | ≤ 35 #/100mL | 560% |
| August 2026 | Ammonia & ammonium- total, daily maximum | .18 mg/L | ≤ 81 ug/L | 122% |
| August 2026 | BOD, 5-day, 20 deg. C, daily maximum | 7.48 mg/L | ≤ 5 mg/L | 50% |
| August 2026 | Enterococci, 90th percentile | 2420 #/100mL | ≤ 130 #/100mL | 1762% |
| August 2026 | Enterococci, geometric mean | 327 #/100mL | ≤ 35 #/100mL | 834% |
| August 2026 | Phosphorus, total [as P], daily maximum | 500 ug/L | ≤ 160 ug/L | 213% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Temperature, water deg. centigrade | daily maximum | ≤ 30 deg C | all year |
| Turbidity | daily maximum | ≤ 50 NTU | all year |
| Turbidity | daily maximum | ≤ 385 NTU | all year |
| Color [PT-CO units] | daily maximum | ≤ 15 col unit (pc) | all year |
| Oxygen, dissolved [DO] | minimum | ≥ 5 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily maximum | ≤ 5 mg/L | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, settleable | daily maximum | report only (mL/L) | all year |
| Phosphorus, total [as P] | daily maximum | ≤ 160 ug/L | all year |
| Copper, total [as Cu] | daily maximum | ≤ 418.46 ug/L | all year |
| Copper, total [as Cu] | daily maximum | ≤ 9.32 ug/L | all year |
| Flow, in conduit or thru treatment plant | daily maximum | ≤ .3049 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Chlorine, total residual | daily maximum | ≤ 11 ug/L | all year |
| Whole Effluent Toxicity [WET] - P. promelas | minimum | report only (%) | all year |
| Whole Effluent Toxicity [WET] - D. magna | minimum | report only (%) | all year |
| Enterococci | geometric mean | ≤ 35 #/100mL | all year |
| Enterococci | 90th percentile | ≤ 130 #/100mL | all year |
| Ammonia & ammonium- total | daily maximum | ≤ 81 ug/L | all year |
Cited limits by parameter: we hold no rule of Puerto Rico's own; the federal ones.
Same industry: the 108 Water Supply permits in Puerto Rico.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/PR0026875 · MCP: https://passage-data.com/mcp