Passage Data · Check a report · Use it from your AI
Water Supply, Carolina, Puerto Rico. NPDES permit PR0026719 expired Jan 31, 2024; its limits still apply. Last 12 months: over a limit 12 times (last August 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| October 2025 | Solids, total dissolved, daily maximum | 560 mg/L | ≤ 500 mg/L | 12% |
| November 2025 | Solids, total dissolved, daily maximum | 1689 mg/L | ≤ 500 mg/L | 238% |
| December 2025 | Solids, total dissolved, daily maximum | 2067 mg/L | ≤ 500 mg/L | 313% |
| January 2026 | Solids, total dissolved, daily maximum | 1305 mg/L | ≤ 500 mg/L | 161% |
| February 2026 | Solids, total dissolved, daily maximum | 1911 mg/L | ≤ 500 mg/L | 282% |
| March 2026 | Solids, total dissolved, daily maximum | 1287 mg/L | ≤ 500 mg/L | 157% |
| April 2026 | Solids, total dissolved, daily maximum | 930 mg/L | ≤ 500 mg/L | 86% |
| May 2026 | Solids, total dissolved, daily maximum | 846 mg/L | ≤ 500 mg/L | 69% |
| June 2026 | Solids, total dissolved, daily maximum | 921 mg/L | ≤ 500 mg/L | 84% |
| July 2026 | Solids, total dissolved, daily maximum | 810 mg/L | ≤ 500 mg/L | 62% |
| August 2026 | BOD, 5-day, 20 deg. C, daily maximum | 6 mg/L | ≤ 5 mg/L | 20% |
| August 2026 | Solids, total dissolved, daily maximum | 981 mg/L | ≤ 500 mg/L | 96% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Temperature, water deg. centigrade | daily maximum | ≤ 32.2 deg C | all year |
| Turbidity | daily maximum | ≤ 50 NTU | all year |
| Color [PT-CO units] | daily maximum | ≤ 15 col unit (pc) | all year |
| Oxygen, dissolved [DO] | instantaneous minimum | ≥ 5 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily maximum | ≤ 5 mg/L | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, settleable | daily maximum | report only (mL/L) | all year |
| Phosphorus, total [as P] | daily maximum | report only (ug/L) | all year |
| Sulfate, total [as SO4] | daily maximum | ≤ 250 mg/L | all year |
| Copper, total [as Cu] | daily maximum | ≤ 8 ug/L | all year |
| Surfactants [MBAS] | daily maximum | ≤ 100 ug/L | all year |
| Flow, in conduit or thru treatment plant | daily maximum | ≤ .157 MGD | all year |
| Chlorine, total residual | daily maximum | ≤ 11 ug/L | all year |
| Enterococci | geometric mean | ≤ 35 #/100mL | all year |
| Enterococci | 90th percentile | ≤ 130 #/100mL | all year |
| Solids, total dissolved | daily maximum | ≤ 500 mg/L | all year |
| Ammonia & ammonium- total | daily maximum | report only (ug/L) | all year |
Cited limits by parameter: we hold no rule of Puerto Rico's own; the federal ones.
Same industry: the 108 Water Supply permits in Puerto Rico.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/PR0026719 · MCP: https://passage-data.com/mcp