Water Supply, Barranquitas, Puerto Rico. NPDES permit PR0026565 expired Apr 30, 2024; its limits still apply. Last 12 months: over a limit once (last August 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| August 2026 | Chlorine, total residual, daily maximum | 310 ug/L | ≤ 11 ug/L | 2718% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Temperature, water deg. centigrade | daily maximum | ≤ 32.2 deg C | all year |
| Temperature, water deg. centigrade | daily maximum | report only (deg C) | all year |
| Turbidity | daily maximum | ≤ 50 NTU | all year |
| Turbidity | daily maximum | report only (NTU) | all year |
| Color [PT-CO units] | daily maximum | ≤ 15 col unit (pc) | all year |
| Color [PT-CO units] | daily maximum | report only (col unit (pc)) | all year |
| Oxygen, dissolved [DO] | instantaneous minimum | ≥ 5 mg/L | all year |
| Oxygen, dissolved [DO] | instantaneous minimum | report only (mg/L) | all year |
| BOD, 5-day, 20 deg. C | daily maximum | ≤ 5 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily maximum | report only (mg/L) | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | minimum | report only (SU) | all year |
| pH | maximum | ≤ 9 SU | all year |
| pH | maximum | report only (SU) | all year |
| Solids, settleable | daily maximum | report only (mL/L) | all year |
| Phosphorus, total [as P] | daily maximum | ≤ 160 ug/L | all year |
| Phosphorus, total [as P] | daily maximum | report only (mg/L) | all year |
| Copper, total [as Cu] | daily maximum | ≤ 10.4 ug/L | all year |
| Copper, total [as Cu] | daily maximum | report only (ug/L) | all year |
| Flow, in conduit or thru treatment plant | daily maximum | ≤ .187 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Chlorine, total residual | daily maximum | ≤ 11 ug/L | all year |
| Solids, total dissolved | daily maximum | ≤ 500 mg/L | all year |
| Solids, total dissolved | daily maximum | report only (mg/L) | all year |
| Ammonia & ammonium- total | daily maximum | report only (ug/L) | all year |
Cited limits by parameter: we hold no rule of Puerto Rico's own; the federal ones.