Water Supply, Cayey, Puerto Rico. NPDES permit PR0026077 expired Oct 31, 2024; its limits still apply. Last 12 months: over a limit 12 times (last August 2026), 10 required values missing, 1 of 16 reports late. Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| October 2025 | BOD, 5-day, 20 deg. C, daily maximum | 9.72 mg/L | ≤ 5 mg/L | 94% |
| November 2025 | Copper, total [as Cu], daily maximum | 382.95 ug/L | ≤ 79.04 ug/L | 385% |
| December 2025 | Copper, total [as Cu], daily maximum | 129.54 ug/L | ≤ 79.04 ug/L | 64% |
| January 2026 | Copper, total [as Cu], daily maximum | 101.28 ug/L | ≤ 79.04 ug/L | 28% |
| January 2026 | Copper, total [as Cu], daily maximum | 101.28 ug/L | ≤ 79.04 ug/L | 28% |
| March 2026 | Copper, total [as Cu], daily maximum | 116.11 ug/L | ≤ 79.04 ug/L | 47% |
| April 2026 | Copper, total [as Cu], daily maximum | 404.41 ug/L | ≤ 79.04 ug/L | 412% |
| May 2026 | BOD, 5-day, 20 deg. C, daily maximum | 6.06 mg/L | ≤ 5 mg/L | 21% |
| May 2026 | Copper, total [as Cu], daily maximum | 353.99 ug/L | ≤ 79.04 ug/L | 348% |
| June 2026 | Copper, total [as Cu], daily maximum | 106.11 ug/L | ≤ 79.04 ug/L | 34% |
| July 2026 | Copper, total [as Cu], daily maximum | 190.18 ug/L | ≤ 79.04 ug/L | 141% |
| August 2026 | Copper, total [as Cu], daily maximum | 148.22 ug/L | ≤ 79.04 ug/L | 88% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Temperature, water deg. centigrade | daily maximum | ≤ 32.2 deg C | all year |
| Turbidity | daily maximum | ≤ 50 NTU | all year |
| Color [PT-CO units] | daily maximum | ≤ 15 col unit (pc) | all year |
| Oxygen, dissolved [DO] | instantaneous minimum | ≥ 5 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily maximum | ≤ 5 mg/L | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, settleable | daily maximum | report only (mL/L) | all year |
| Copper, total [as Cu] | daily maximum | ≤ 9.98 ug/L | all year |
| Copper, total [as Cu] | daily maximum | ≤ 79.04 ug/L | all year |
| Lead, total [as Pb] | daily maximum | ≤ 7.9 ug/L | all year |
| Lead, total [as Pb] | daily maximum | ≤ 7.9 ug/L | all year |
| Pentachlorophenol | daily maximum | ≤ 1 ug/L | all year |
| Pentachlorophenol | daily maximum | report only (ug/L) | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Flow, in conduit or thru treatment plant | daily maximum | ≤ .337 MGD | all year |
| Chlorine, total residual | daily maximum | ≤ 11 ug/L | all year |
| Cyanide, free available | daily maximum | ≤ 5.2 ug/L | all year |
| Solids, total dissolved | daily maximum | ≤ 500 mg/L | all year |
| Solids, total dissolved | daily maximum | report only (mg/L) | all year |
| Mercury, total [as Hg] | daily maximum | ≤ .05 ug/L | all year |
| Mercury, total [as Hg] | daily maximum | report only (ug/L) | all year |
| Ammonia & ammonium- total | daily maximum | report only (ug/L) | all year |
Cited limits by parameter: we hold no rule of Puerto Rico's own; the federal ones.
Same industry: the 108 Water Supply permits in Puerto Rico.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/PR0026077 · MCP: https://passage-data.com/mcp