Passage Data · Check a report · Use it from your AI
Water Supply, Ponce, Puerto Rico. NPDES permit PR0024651 expired Jan 31, 2024; its limits still apply. Last 12 months: over a limit 4 times (last March 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| November 2025 | Turbidity, daily maximum | 55 NTU | ≤ 50 NTU | — |
| February 2026 | Phosphorus, total [as P], daily maximum | 5280 ug/L | ≤ 5000 ug/L | 6% |
| February 2026 | Turbidity, daily maximum | 190 NTU | ≤ 50 NTU | — |
| March 2026 | Chlorine, total residual, daily maximum | 150 ug/L | ≤ 11 ug/L | 1264% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Temperature, water deg. centigrade | daily maximum | ≤ 32.2 deg C | all year |
| Turbidity | daily maximum | ≤ 50 NTU | all year |
| Color [PT-CO units] | daily maximum | ≤ 15 col unit (pc) | all year |
| Oxygen, dissolved [DO] | instantaneous minimum | ≥ 5 mg/L | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, settleable | daily maximum | report only (mL/L) | all year |
| Phosphorus, total [as P] | daily maximum | ≤ 160 ug/L | all year |
| Phosphorus, total [as P] | daily maximum | ≤ 5000 ug/L | all year |
| Sulfate, total [as SO4] | daily maximum | report only (mg/L) | all year |
| Cadmium, total [as Cd] | daily maximum | ≤ .31 ug/L | all year |
| Cadmium, total [as Cd] | daily maximum | ≤ 1.4 ug/L | all year |
| Copper, total [as Cu] | daily maximum | ≤ 10.8 ug/L | all year |
| Copper, total [as Cu] | daily maximum | ≤ 76.91 ug/L | all year |
| Lead, total [as Pb] | daily maximum | ≤ 3.97 ug/L | all year |
| Lead, total [as Pb] | daily maximum | ≤ 10 ug/L | all year |
| Surfactants [MBAS] | daily maximum | ≤ 100 ug/L | all year |
| Flow, in conduit or thru treatment plant | daily maximum | ≤ .006 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Chlorine, total residual | daily maximum | ≤ 11 ug/L | all year |
| Cyanide, free available | daily maximum | ≤ 5.2 ug/L | all year |
| Solids, total dissolved | daily maximum | ≤ 500 mg/L | all year |
| Mercury, total [as Hg] | daily maximum | ≤ .05 ug/L | all year |
| Ammonia & ammonium- total | daily maximum | report only (ug/L) | all year |
Cited limits by parameter: we hold no rule of Puerto Rico's own; the federal ones.
Same industry: the 108 Water Supply permits in Puerto Rico.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/PR0024651 · MCP: https://passage-data.com/mcp