Passage Data · Check a report · Use it from your AI
Water Supply, Arecibo, Puerto Rico. NPDES permit PR0024210 expired Aug 31, 2026; its limits still apply. Last 12 months: over a limit 4 times (last July 2026), 1 of 16 reports late. Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| December 2025 | BOD, 5-day, 20 deg. C, daily maximum | > 226 mg/L | ≤ 59 mg/L | — |
| December 2025 | pH, minimum | 5.69 SU | ≥ 6 SU | — |
| January 2026 | BOD, 5-day, 20 deg. C, daily maximum | 137 mg/L | ≤ 59 mg/L | 132% |
| July 2026 | BOD, 5-day, 20 deg. C, daily maximum | 148 mg/L | ≤ 59 mg/L | 151% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Temperature, water deg. centigrade | daily maximum | ≤ 30 deg C | all year |
| Turbidity | daily maximum | ≤ 50 NTU | all year |
| Turbidity | daily maximum | ≤ 4402 NTU | all year |
| Color [PT-CO units] | daily maximum | ≤ 15 col unit (pc) | all year |
| Color [PT-CO units] | daily maximum | ≤ 25 col unit (pc) | all year |
| Oxygen, dissolved [DO] | instantaneous minimum | ≥ 5 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily maximum | ≤ 5 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily maximum | ≤ 59 mg/L | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, settleable | daily maximum | report only (mL/L) | all year |
| Oil & Grease | daily maximum | report only (mg/L) | all year |
| Phosphorus, total [as P] | daily maximum | ≤ 160 ug/L | all year |
| Phosphorus, total [as P] | daily maximum | ≤ 5.1 mg/L | all year |
| Cyanide, total [as CN] | daily maximum | ≤ 4 ug/L | all year |
| Sulfate, total [as SO4] | daily maximum | report only (ug/L) | all year |
| Arsenic, total [as As] | daily maximum | ≤ 10 ug/L | all year |
| Chromium, hexavalent [as Cr] | daily maximum | report only (ug/L) | all year |
| Copper, total [as Cu] | daily maximum | ≤ 9.33 ug/L | all year |
| Copper, total [as Cu] | daily maximum | ≤ 400.6 ug/L | all year |
| Lead, total [as Pb] | daily maximum | ≤ 3.18 ug/L | all year |
| Lead, total [as Pb] | daily maximum | ≤ 74 ug/L | all year |
| Zinc, total [as Zn] | daily maximum | ≤ 119.82 ug/L | all year |
| Zinc, total [as Zn] | daily maximum | ≤ 344.82 ug/L | all year |
| Flow, in conduit or thru treatment plant | daily maximum | ≤ .26 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Chlorine, total residual | daily maximum | ≤ 11 ug/L | all year |
| Whole Effluent Toxicity [WET] - P. promelas | minimum | report only (%) | all year |
| Whole Effluent Toxicity [WET] - D. magna | minimum | report only (%) | all year |
| Solids, total dissolved | daily maximum | ≤ 500 mg/L | all year |
| Ammonia & ammonium- total | daily maximum | report only (mg/L) | all year |
Cited limits by parameter: we hold no rule of Puerto Rico's own; the federal ones.
Same industry: the 108 Water Supply permits in Puerto Rico.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/PR0024210 · MCP: https://passage-data.com/mcp