Passage Data · Check a report · Use it from your AI
Water Supply, Jayuya, Puerto Rico. NPDES permit PR0024121, in force until Nov 30, 2027. Last 12 months: over a limit 9 times (last July 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| December 2025 | Ammonia & ammonium- total, daily maximum | 12.6 mg/L | ≤ .179 mg/L | 6939% |
| December 2025 | BOD, 5-day, 20 deg. C, daily maximum | 12.8 mg/L | ≤ 9.8 mg/L | 31% |
| January 2026 | Ammonia & ammonium- total, daily maximum | .3 mg/L | ≤ .179 mg/L | 68% |
| March 2026 | Ammonia & ammonium- total, daily maximum | 12.65 mg/L | ≤ .179 mg/L | 6967% |
| March 2026 | BOD, 5-day, 20 deg. C, daily maximum | 63 mg/L | ≤ 9.8 mg/L | 543% |
| April 2026 | Lead, total [as Pb], daily maximum | 4.3 ug/L | ≤ 1.57 ug/L | 174% |
| May 2026 | Phosphorus, total [as P], daily maximum | 3190 ug/L | ≤ 1000 ug/L | 219% |
| July 2026 | Copper, total [as Cu], daily maximum | 389.38 ug/L | ≤ 370.8 ug/L | 5% |
| July 2026 | Lead, total [as Pb], daily maximum | 3.75 ug/L | ≤ 1.57 ug/L | 139% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Temperature, water deg. centigrade | daily maximum | ≤ 30 deg C | all year |
| Turbidity | daily maximum | ≤ 50 NTU | all year |
| Turbidity | daily maximum | ≤ 349.5 NTU | all year |
| Color [PT-CO units] | daily maximum | ≤ 15 col unit (pc) | all year |
| Color [PT-CO units] | daily maximum | ≤ 93 col unit (pc) | all year |
| Oxygen, dissolved [DO] | instantaneous minimum | ≥ 3 mg/L | all year |
| Oxygen, dissolved [DO] | instantaneous minimum | ≥ 5 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily maximum | ≤ 5 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily maximum | ≤ 9.8 mg/L | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, settleable | daily maximum | report only (mL/L) | all year |
| Phosphorus, total [as P] | daily maximum | ≤ 160 ug/L | all year |
| Phosphorus, total [as P] | daily maximum | ≤ 1000 ug/L | all year |
| Copper, total [as Cu] | daily maximum | ≤ 5.8 ug/L | all year |
| Copper, total [as Cu] | daily maximum | ≤ 370.8 ug/L | all year |
| Lead, total [as Pb] | daily maximum | ≤ 1.57 ug/L | all year |
| Flow, in conduit or thru treatment plant | daily maximum | ≤ .14 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Chlorine, total residual | daily maximum | ≤ 11 ug/L | all year |
| Whole Effluent Toxicity [WET] - P. promelas | minimum | report only (%) | all year |
| Whole Effluent Toxicity [WET] - D. magna | minimum | report only (%) | all year |
| Solids, total dissolved | daily maximum | ≤ 500 mg/L | all year |
| Mercury, total [as Hg] | daily maximum | ≤ .05 ug/L | all year |
| Ammonia & ammonium- total | daily maximum | ≤ .179 mg/L | all year |
Cited limits by parameter: we hold no rule of Puerto Rico's own; the federal ones.
Same industry: the 108 Water Supply permits in Puerto Rico.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/PR0024121 · MCP: https://passage-data.com/mcp