Passage Data · Check a report · Use it from your AI

Prasa Aguadilla WTP

Water Supply, major discharger, Aguadilla, Puerto Rico. NPDES permit PR0022918 expired Nov 30, 2024; its limits still apply. Last 12 months: over a limit 3 times (last July 2026). Source: EPA ECHO, Oct 22, 2026.

Reports due
About 28 days after each period: form A monthly (16 values), form Q quarterly
Last report on file
August 2026
Oct 2024 – Sep 2025
3 values over a limit, 0 required values missing, 0 of 16 reports late

Last 12 months (Oct 1, 2025 – Sep 30, 2026)

Period endingParameterReportedLimitOver by
November 2025BOD, 5-day, 20 deg. C, daily maximum20.6 mg/L≤ 18 mg/L14%
May 2026BOD, 5-day, 20 deg. C, daily maximum32.6 mg/L≤ 18 mg/L81%
July 2026BOD, 5-day, 20 deg. C, daily maximum22.5 mg/L≤ 18 mg/L25%

Limits in force (30)

ParameterStatisticLimitMonths
Temperature, water deg. centigradedaily maximum≤ 30 deg Call year
Temperature, water deg. centigradedaily maximumreport only (deg C)all year
Turbiditydaily maximum≤ 50 NTUall year
Turbiditydaily maximum≤ 3000 NTUall year
Color [PT-CO units]daily maximum≤ 15 col unit (pc)all year
Oxygen, dissolved [DO]instantaneous minimum≥ 5 mg/Lall year
BOD, 5-day, 20 deg. Cdaily maximum≤ 5 mg/Lall year
BOD, 5-day, 20 deg. Cdaily maximum≤ 18 mg/Lall year
pHminimum≥ 6 SUall year
pHmaximum≤ 9 SUall year
Solids, settleabledaily maximumreport only (mL/L)all year
Phosphorus, total [as P]daily maximum≤ 160 ug/Lall year
Phosphorus, total [as P]daily maximum≤ 6.52 mg/Lall year
Cyanide, total [as CN]daily maximum≤ 4 ug/Lall year
Cyanide, total [as CN]daily maximumreport only (ug/L)all year
Arsenic, total [as As]daily maximum≤ 10 ug/Lall year
Arsenic, total [as As]daily maximumreport only (ug/L)all year
Copper, total [as Cu]daily maximum≤ 10.18 ug/Lall year
Copper, total [as Cu]daily maximum≤ 334 ug/Lall year
Lead, total [as Pb]daily maximum≤ 3.62 ug/Lall year
Lead, total [as Pb]daily maximumreport only (ug/L)all year
Zinc, total [as Zn]daily maximum≤ 130.67 ug/Lall year
Zinc, total [as Zn]daily maximum≤ 301.68 ug/Lall year
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year
Flow, in conduit or thru treatment plantdaily maximum≤ 1.902 MGDall year
Chlorine, total residualdaily maximum≤ 11 ug/Lall year
Sulfide-hydrogen sulfide [undissociated]daily maximum≤ 2 ug/Lall year
Mercury, total [as Hg]daily maximum≤ .05 ug/Lall year
Mercury, total [as Hg]daily maximum≤ .305 ug/Lall year
Ammonia & ammonium- totaldaily maximumreport only (ug/L)all year

How strict are these limits?

Cited limits by parameter: we hold no rule of Puerto Rico's own; the federal ones.

Same industry: the 108 Water Supply permits in Puerto Rico.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/PR0022918 · MCP: https://passage-data.com/mcp