Passage Data · Check a report · Use it from your AI
Water Supply, Yabucoa, Puerto Rico. NPDES permit PR0022799, in force until Sep 30, 2030. Last 12 months: over a limit 10 times (last July 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| October 2025 | Phosphorus, total [as P], daily maximum | 1600 ug/L | ≤ 160 ug/L | 900% |
| November 2025 | Phosphorus, total [as P], daily maximum | 1360 ug/L | ≤ 160 ug/L | 750% |
| December 2025 | Phosphorus, total [as P], daily maximum | 3730 ug/L | ≤ 160 ug/L | 2231% |
| December 2025 | Turbidity, daily maximum | 100 NTU | ≤ 50 NTU | — |
| March 2026 | Phosphorus, total [as P], daily maximum | 5740 ug/L | ≤ 160 ug/L | 3488% |
| March 2026 | Turbidity, daily maximum | 260 NTU | ≤ 50 NTU | — |
| April 2026 | Phosphorus, total [as P], daily maximum | 2440 ug/L | ≤ 160 ug/L | 1425% |
| June 2026 | Phosphorus, total [as P], daily maximum | 6790 ug/L | ≤ 160 ug/L | 4144% |
| June 2026 | Turbidity, daily maximum | 330 NTU | ≤ 50 NTU | — |
| July 2026 | Phosphorus, total [as P], daily maximum | 3280 ug/L | ≤ 160 ug/L | 1950% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Temperature, water deg. centigrade | daily maximum | ≤ 30 deg C | all year |
| Turbidity | daily maximum | ≤ 50 NTU | all year |
| Color [PT-CO units] | daily maximum | ≤ 15 col unit (pc) | all year |
| Oxygen, dissolved [DO] | instantaneous minimum | ≥ 5 mg/L | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, settleable | daily maximum | report only (mL/L) | all year |
| Phosphorus, total [as P] | daily maximum | ≤ 160 ug/L | all year |
| Cadmium, total [as Cd] | daily maximum | ≤ .41 ug/L | all year |
| Copper, total [as Cu] | daily maximum | ≤ 4.6 ug/L | all year |
| Copper, total [as Cu] | daily maximum | ≤ 76.13 ug/L | all year |
| Lead, total [as Pb] | daily maximum | ≤ 1.1 ug/L | all year |
| Lead, total [as Pb] | daily maximum | ≤ 10.9 ug/L | all year |
| Flow, in conduit or thru treatment plant | daily maximum | ≤ .03 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Chlorine, total residual | daily maximum | ≤ 11 ug/L | all year |
Cited limits by parameter: we hold no rule of Puerto Rico's own; the federal ones.
Same industry: the 108 Water Supply permits in Puerto Rico.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/PR0022799 · MCP: https://passage-data.com/mcp