Passage Data · Check a report · Use it from your AI

Prasa Cedro Arriba WTP

Water Supply, Naranjito, Puerto Rico. NPDES permit PR0022659 expired Oct 31, 2024; its limits still apply. Last 12 months: over a limit 5 times (last July 2026). Source: EPA ECHO, Oct 22, 2026.

Reports due
About 28 days after each period: form A monthly (15 values), form Q quarterly, form Y yearly
Last report on file
August 2026
Oct 2024 – Sep 2025
3 values over a limit, 0 required values missing, 1 of 17 reports late

Last 12 months (Oct 1, 2025 – Sep 30, 2026)

Period endingParameterReportedLimitOver by
November 2025Color [PT-CO units], daily maximum20 col unit (pc)≤ 15 col unit (pc)—
November 2025Phosphorus, total [as P], daily maximum7.06 mg/L≤ 5 mg/L41%
May 2026pH, minimum5.11 SU≥ 6 SU—
July 2026Chlorine, total residual, daily maximum440 ug/L≤ 11 ug/L3900%
July 2026pH, minimum5.35 SU≥ 6 SU—

Limits in force (25)

ParameterStatisticLimitMonths
Temperature, water deg. centigradedaily maximum≤ 32.2 deg Call year
Turbiditydaily maximum≤ 50 NTUall year
Turbiditydaily maximum≤ 4000 NTUall year
Color [PT-CO units]daily maximum≤ 15 col unit (pc)all year
Oxygen, dissolved [DO]instantaneous minimum≥ 5 mg/Lall year
BOD, 5-day, 20 deg. Cdaily maximum≤ 5 mg/Lall year
BOD, 5-day, 20 deg. Cdaily maximum≤ 45 mg/Lall year
pHminimum≥ 6 SUall year
pHmaximum≤ 9 SUall year
Solids, settleabledaily maximumreport only (mL/L)all year
Phosphorus, total [as P]daily maximum≤ 160 ug/Lall year
Phosphorus, total [as P]daily maximum≤ 5 mg/Lall year
Arsenic, total [as As]daily maximum≤ 10 ug/Lall year
Arsenic, total [as As]daily maximumreport only (ug/L)all year
Copper, total [as Cu]daily maximum≤ 11 ug/Lall year
Copper, total [as Cu]daily maximum≤ 67 ug/Lall year
Lead, total [as Pb]daily maximum≤ 4.3 ug/Lall year
Lead, total [as Pb]daily maximum≤ 7.77 ug/Lall year
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year
Flow, in conduit or thru treatment plantdaily maximum≤ .1728 MGDall year
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year
Chlorine, total residualdaily maximum≤ 11 ug/Lall year
Mercury, total [as Hg]daily maximum≤ .05 ug/Lall year
Mercury, total [as Hg]daily maximumreport only (ug/L)all year
Ammonia & ammonium- totaldaily maximumreport only (ug/L)all year

How strict are these limits?

Cited limits by parameter: we hold no rule of Puerto Rico's own; the federal ones.

Same industry: the 108 Water Supply permits in Puerto Rico.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history