Passage Data · Check a report · Use it from your AI
Water Supply, major discharger, Guaynabo, Puerto Rico. NPDES permit PR0022438 expired Aug 31, 2026; its limits still apply. Last 12 months: over a limit 4 times (last June 2026), 2 of 13 reports late. Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| October 2025 | BOD, 5-day, 20 deg. C, daily maximum | 7.1 mg/L | ≤ 5 mg/L | 42% |
| February 2026 | BOD, 5-day, 20 deg. C, daily maximum | 32.5 mg/L | ≤ 5 mg/L | 550% |
| June 2026 | Copper, total [as Cu], daily maximum | 110.73 ug/L | ≤ 65.29 ug/L | 70% |
| June 2026 | Phosphorus, total [as P], daily maximum | 8.25 mg/L | ≤ 4.2 mg/L | 96% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Temperature, water deg. centigrade | daily maximum | ≤ 30 deg C | all year |
| Turbidity | daily maximum | ≤ 50 NTU | all year |
| Turbidity | daily maximum | ≤ 500 NTU | all year |
| Color [PT-CO units] | daily maximum | ≤ 15 col unit (pc) | all year |
| Oxygen, dissolved [DO] | instantaneous minimum | ≥ 5 mg/L | all year |
| Oxygen, dissolved [DO] | instantaneous minimum | ≥ 4 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily maximum | ≤ 5 mg/L | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, settleable | daily maximum | report only (mL/L) | all year |
| Phosphorus, total [as P] | daily maximum | ≤ 160 ug/L | all year |
| Phosphorus, total [as P] | daily maximum | ≤ 4.2 mg/L | all year |
| Copper, total [as Cu] | daily maximum | ≤ 10.84 ug/L | all year |
| Copper, total [as Cu] | daily maximum | ≤ 65.29 ug/L | all year |
| Flow, in conduit or thru treatment plant | daily maximum | ≤ 2.37 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Chlorine, total residual | daily maximum | ≤ 11 ug/L | all year |
| Whole Effluent Toxicity [WET] - P. promelas | minimum | report only (%) | all year |
| Whole Effluent Toxicity [WET] - D. magna | minimum | report only (%) | all year |
| Ammonia & ammonium- total | daily maximum | report only (ug/L) | all year |
Cited limits by parameter: we hold no rule of Puerto Rico's own; the federal ones.
Same industry: the 108 Water Supply permits in Puerto Rico.
· Save this facility as a site · Superfund sites nearby · Your permits on one board