Passage Data · Check a report · Use it from your AI
Water Supply, major discharger, Trujillo Alto, Puerto Rico. NPDES permit PR0022411 expired Nov 30, 2024; its limits still apply. Last 12 months: over a limit once (last July 2026), 2 of 16 reports late. Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| July 2026 | Oxygen, dissolved [DO], instantaneous minimum | 2.7 mg/L | ≥ 3 mg/L | 10% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Temperature, water deg. centigrade | daily maximum | ≤ 30 deg C | all year |
| Turbidity | daily maximum | ≤ 50 NTU | all year |
| Turbidity | daily maximum | ≤ 5119 NTU | all year |
| Color [PT-CO units] | daily maximum | ≤ 15 col unit (pc) | all year |
| Color [PT-CO units] | daily maximum | ≤ 30 col unit (pc) | all year |
| Oxygen, dissolved [DO] | instantaneous minimum | ≥ 5 mg/L | all year |
| Oxygen, dissolved [DO] | instantaneous minimum | ≥ 3 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily maximum | ≤ 5 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily maximum | ≤ 69.99 mg/L | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, settleable | daily maximum | report only (mL/L) | all year |
| Phosphorus, total [as P] | daily maximum | ≤ 160 ug/L | all year |
| Phosphorus, total [as P] | daily maximum | ≤ 6.61 mg/L | all year |
| Copper, total [as Cu] | daily maximum | ≤ 300 ug/L | all year |
| Lead, total [as Pb] | daily maximum | ≤ 3.24 ug/L | all year |
| Lead, total [as Pb] | daily maximum | report only (ug/L) | all year |
| Zinc, total [as Zn] | daily maximum | ≤ 121.38 ug/L | all year |
| Zinc, total [as Zn] | daily maximum | ≤ 325.25 ug/L | all year |
| Pentachlorophenol | daily maximum | ≤ .3 ug/L | all year |
| Pentachlorophenol | daily maximum | report only (ug/L) | all year |
| Flow, in conduit or thru treatment plant | daily maximum | ≤ 6 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Chlorine, total residual | daily maximum | ≤ 11 ug/L | all year |
| Solids, total dissolved | daily maximum | ≤ 500 mg/L | all year |
| Solids, total dissolved | daily maximum | report only (mg/L) | all year |
| Mercury, total [as Hg] | daily maximum | report only (ug/L) | all year |
| Ammonia & ammonium- total | daily maximum | report only (ug/L) | all year |
Cited limits by parameter: we hold no rule of Puerto Rico's own; the federal ones.
Same industry: the 108 Water Supply permits in Puerto Rico.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/PR0022411 · MCP: https://passage-data.com/mcp