Passage Data · Check a report · Use it from your AI

Puerto Rico Electric PWR Auth

Electric Services, major discharger, Toa Baja, Puerto Rico. NPDES permit PR0001031 expired Mar 31, 2021; its limits still apply. Last 12 months: over a limit 10 times (last August 2026), 6 of 68 reports late. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 28 days after each period: outfall 001 form A monthly (19 values), outfall 001 form C monthly (18 values), outfall 002 form A monthly (14 values), outfall 01A form 2 monthly (9 values), outfall 01A form 3 monthly (7 values), outfall 01C form 1 monthly (18 values), and 2 more forms
Last report on file
August 2026
Oct 2024 – Sep 2025
6 values over a limit, 0 required values missing, 0 of 74 reports late

Last 12 months (Oct 1, 2025 – Sep 30, 2026)

Period endingParameterReportedLimitOver by
October 2025Copper, total [as Cu], daily maximum3.88 ug/L≤ 3.73 ug/L4%
October 2025Solids, total suspended, monthly average32.3 mg/L≤ 30 mg/L8%
January 2026Solids, total suspended, monthly average33 mg/L≤ 30 mg/L10%
April 2026Cyanide, free available, daily maximum1.1 ug/L≤ 1 ug/L10%
April 2026Cyanide, free available, daily maximum2.9 ug/L≤ 1 ug/L190%
May 2026Solids, total suspended, monthly average37 mg/L≤ 30 mg/L23%
June 2026Cyanide, free available, daily maximum1.7 ug/L≤ 1 ug/L70%
June 2026Solids, total suspended, monthly average36 mg/L≤ 30 mg/L20%
August 2026Copper, total [as Cu], daily maximum4.61 ug/L≤ 3.73 ug/L24%
August 2026Cyanide, free available, daily maximum1.7 ug/L≤ 1 ug/L70%

Limits in force (99)

ParameterStatisticLimitMonthsOutfall
Temperature, water deg. centigradedaily maximum≤ 40.4 deg Call year001
Temperature, water deg. centigradedaily maximum≤ 32.2 deg Call year001
Temperature, water deg. fahrenheitdaily maximumreport only (deg F)all year001
Turbiditydaily maximum≤ 10 NTUall year001
Turbiditydaily maximum≤ 10 NTUall year001
Color [PT-CO units]daily maximumreport only (col unit (pc))all year001
Color [PT-CO units]daily maximumreport only (col unit (pc))all year001
Oxygen, dissolved [DO]instantaneous minimum≥ 4 mg/Lall year001
Oxygen, dissolved [DO]instantaneous minimum≥ 4 mg/Lall year001
BOD, 5-day, 20 deg. Cdaily maximum≤ 30 mg/Lall year001
BOD, 5-day, 20 deg. Cdaily maximum≤ 30 mg/Lall year001
pHminimum≥ 7.3 SUall year001
pHminimum≥ 7.3 SUall year001
pHmaximum≤ 8.5 SUall year001
pHmaximum≤ 8.5 SUall year001
Solids, total suspendedmonthly average≤ 30 mg/Lall year001
Solids, total suspendedweekly average≤ 100 mg/Lall year001
Solids, total suspendeddaily maximumreport only (mg/L)all year001
Solids, settleabledaily maximumreport only (mL/L)all year001
Solids, settleabledaily maximumreport only (mL/L)all year001
Oil & Greasedaily maximumreport only (mg/L)all year001
Oil & Greasedaily maximumreport only (mg/L)all year001
Oil & Greasemonthly average≤ 15 mg/Lall year001
Oil & Greasemonthly average≤ 15 mg/Lall year001
Oil & Greasedaily maximum≤ 20 mg/Lall year001
Oil & Greasedaily maximum≤ 20 mg/Lall year001
Arsenic, total [as As]daily maximum≤ 36 ug/Lall year001
Cadmium, total [as Cd]daily maximumreport only (ug/L)all year001
Chromium, hexavalent [as Cr]daily maximum≤ 50.35 ug/Lall year001
Copper, total [as Cu]daily maximum≤ 3.73 ug/Lall year001
Copper, total [as Cu]daily maximum≤ 3.73 ug/Lall year001
Thallium, total [as Tl]daily maximum≤ .47 ug/Lall year001
Thallium, total [as Tl]daily maximum≤ .47 ug/Lall year001
Nickel, total [as Ni]daily maximumreport only (ug/L)all year001
Nickel, total [as Ni]daily maximum≤ 8.28 ug/Lall year001
Silver, total [as Ag]daily maximum≤ 2.24 ug/Lall year001
Pentachlorophenoldaily maximumreport only (ug/L)all year001
Pentachlorophenoldaily maximumreport only (ug/L)all year001
Polychlorinated biphenyls [PCBs]daily maximumreport only (ug/L)all year001
Polychlorinated biphenyls [PCBs]daily maximumreport only (ug/L)all year001
Flow, in conduit or thru treatment plantdaily maximum≤ 652 MGDall year001
Flow, in conduit or thru treatment plantdaily maximum≤ .74 MGDall year001
Chlorine, total residualdaily maximum≤ .2 mg/Lall year001
Cyanide, free availabledaily maximum≤ 1 ug/Lall year001
Cyanide, free availabledaily maximum≤ 1 ug/Lall year001
Sulfide-hydrogen sulfide [undissociated]daily maximum≤ 2 ug/Lall year001
Sulfide-hydrogen sulfide [undissociated]daily maximum≤ 2 ug/Lall year001
Nitrogen, Totaldaily maximumreport only (ug/L)all year001
Sulfates, total [as SO4]daily maximum≤ 2800 mg/Lall year001
Mercury, total [as Hg]daily maximum≤ .051 ug/Lall year001
Mercury, total [as Hg]daily maximum≤ .051 ug/Lall year001
Temperature, water deg. centigradedaily maximum≤ 32.2 deg Call year002
Turbiditydaily maximum≤ 10 NTUall year002
Color [PT-CO units]daily maximumreport only (col unit (pc))all year002
Oxygen, dissolved [DO]instantaneous minimum≥ 4 mg/Lall year002
Oxygen demand, chem. [high level] [COD]daily maximum≤ 100 mg/Lall year002
pHminimum≥ 7.3 SUall year002
pHmaximum≤ 8.5 SUall year002
Solids, settleabledaily maximumreport only (mL/L)all year002
Oil & Greasedaily maximumreport only (ug/L)all year002
Oil & Greasemonthly average≤ 15 mg/Lall year002
Oil & Greasedaily maximum≤ 20 mg/Lall year002
Nickel, total [as Ni]daily maximumreport only (ug/L)all year002
Polychlorinated biphenyls [PCBs]daily maximumreport only (ug/L)all year002
Priority Pollutantsdaily maximumreport only (ug/L)all year002
pHminimum≥ 6 SUall year01A
pHminimum≥ 6 SUall year01A
pHmaximum≤ 9 SUall year01A
pHmaximum≤ 9 SUall year01A
Solids, total suspendeddaily average≤ 30 mg/Lall year01A
Solids, total suspendeddaily maximum≤ 100 mg/Lall year01A
Oil & Greasedaily average≤ 15 mg/Lall year01A
Oil & Greasedaily maximum≤ 20 mg/Lall year01A
Zinc, total [as Zn]daily average≤ 1 mg/Lall year01A
Zinc, total [as Zn]daily maximum≤ 1 mg/Lall year01A
Flow, in conduit or thru treatment plantdaily maximumreport only (gal/d)all year01A
Flow, in conduit or thru treatment plantdaily maximumreport only (gal/d)all year01A
Chlorine, total residualdaily maximum≤ .2 mg/Lall year01A
Chlorine, free availabledaily average≤ .2 mg/Lall year01A
Chlorine, free availabledaily maximum≤ .5 mg/Lall year01A
Priority Pollutant Resultsdaily maximum≤ 0 pass=0;fail=1all year01A
pHminimum≥ 6 SUall year01C
pHmaximum≤ 9 SUall year01C
Solids, total suspendeddaily average≤ 51.1 kg/dall year01C
Solids, total suspendeddaily maximum≤ 170.4 kg/dall year01C
Oil & Greasedaily average≤ 25.6 mg/Lall year01C
Oil & Greasedaily maximum≤ 34.1 mg/Lall year01C
Chromium, total [as Cr]daily average≤ .2 mg/Lall year01C
Chromium, total [as Cr]daily maximum≤ .2 mg/Lall year01C
Copper, total [as Cu]daily average≤ 1.7 kg/dall year01C
Copper, total [as Cu]daily maximum≤ 1.7 kg/dall year01C
Iron, total [as Fe]daily average≤ 1.7 kg/dall year01C
Iron, total [as Fe]daily maximum≤ 1.7 kg/dall year01C
Zinc, total [as Zn]daily average≤ 1 mg/Lall year01C
Zinc, total [as Zn]daily maximum≤ 1 mg/Lall year01C
Flow, in conduit or thru treatment plantdaily maximum≤ .74 MGDall year01C
Chlorine, total residualdaily maximum≤ .2 mg/Lall year01C
Chlorine, free availabledaily average≤ .2 mg/Lall year01C
Chlorine, free availabledaily maximum≤ .5 mg/Lall year01C

How strict are these limits?

Cited limits by parameter: we hold no rule of Puerto Rico's own; the federal ones.

Same industry: the 5 Electric Services permits in Puerto Rico.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history