Passage Data · Check a report · Use it from your AI

Red Lion Boro Muni Auth York Cnty

Water Supply, Windsor, Pennsylvania. NPDES permit PA0261581, in force until Apr 30, 2028. Last 12 months: no values over a limit, 23 required values missing. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 28 days after each period: outfall 001 form A monthly (22 values), outfall 002 form A monthly (1 value)
Renewal application due
Nov 2, 2027 · 180 days before expiry; your permit may set another date
Last report on file
June 2026
Oct 2024 – Sep 2025
0 values over a limit, 0 required values missing, 0 of 24 reports late

Limits in force (23)

ParameterStatisticLimitMonthsOutfall
pHinstantaneous minimum≥ 6 SUall year001
pHinstantaneous maximum≤ 9 SUall year001
Solids, total suspendedmonthly average≤ 30 mg/Lall year001
Solids, total suspendeddaily maximum≤ 60 mg/Lall year001
Solids, total suspendedmonthly averagereport only (lb/d)all year001
Solids, total suspendeddaily maximumreport only (lb/d)all year001
Copper, total [as Cu]monthly average≤ .012 mg/Lall year001
Copper, total [as Cu]daily maximum≤ .019 mg/Lall year001
Copper, total [as Cu]monthly average≤ .035 lb/dall year001
Copper, total [as Cu]daily maximum≤ .054 lb/dall year001
Manganese, total [as Mn]monthly averagereport only (mg/L)all year001
Manganese, total [as Mn]daily maximumreport only (mg/L)all year001
Manganese, total [as Mn]monthly averagereport only (lb/d)all year001
Manganese, total [as Mn]daily maximumreport only (lb/d)all year001
Aluminum, total [as Al]monthly average≤ .85 mg/Lall year001
Aluminum, total [as Al]daily maximum≤ 1.33 mg/Lall year001
Aluminum, total [as Al]monthly average≤ 2.49 lb/dall year001
Aluminum, total [as Al]daily maximum≤ 3.89 lb/dall year001
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year001
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year001
Chlorine, total residualmonthly average≤ .12 mg/Lall year001
Chlorine, total residualinstantaneous maximum≤ .4 mg/Lall year001
Chlorine, total residualinstantaneous maximumreport only (mg/L)all year002

How strict are these limits?

Cited limits by parameter: Pennsylvania's rules and the federal ones.

Same industry: the 214 Water Supply permits in Pennsylvania.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/PA0261581 · MCP: https://passage-data.com/mcp