Passage Data · Check a report · Use it from your AI

Coaldale Six Mile Run Water

Water Supply, Six Mile Run, Pennsylvania. NPDES permit PA0260479 expired Oct 31, 2020; its limits still apply. Last 12 months: no values over a limit, 29 required values missing. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 28 days after each period: outfall 001 form A monthly (17 values), outfall 002 form A monthly (4 values), outfall 003 form A monthly (4 values), outfall 003 form Q quarterly (6 values), outfall 004 form A monthly (4 values), outfall 004 form Q quarterly (6 values)
Last report on file
June 2026
Oct 2024 – Sep 2025
0 values over a limit, 29 required values missing, 4 of 56 reports late

Limits in force (41)

ParameterStatisticLimitMonthsOutfall
pHminimum≥ 6 SUall year001
pHinstantaneous maximum≤ 9 SUall year001
Solids, total suspendedmonthly average≤ 30 mg/Lall year001
Solids, total suspendeddaily maximum≤ 60 mg/Lall year001
Iron, total [as Fe]monthly average≤ 2 mg/Lall year001
Iron, total [as Fe]daily maximum≤ 4 mg/Lall year001
Iron, total [as Fe]monthly averagereport only (lb/d)all year001
Manganese, total [as Mn]monthly average≤ 1 mg/Lall year001
Manganese, total [as Mn]daily maximum≤ 2 mg/Lall year001
Manganese, total [as Mn]monthly averagereport only (lb/d)all year001
Aluminum, total [as Al]monthly average≤ 4 mg/Lall year001
Aluminum, total [as Al]daily maximum≤ 8 mg/Lall year001
Aluminum, total [as Al]monthly averagereport only (lb/d)all year001
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year001
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year001
Chlorine, total residualmonthly average≤ .5 mg/Lall year001
Chlorine, total residualinstantaneous maximum≤ 1 mg/Lall year001
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year002
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year002
Chlorine, total residualmonthly average≤ .5 mg/Lall year002
Chlorine, total residualinstantaneous maximum≤ 1 mg/Lall year002
Solids, total suspendedmonthly average≤ 30 mg/Lall year003
Solids, total suspendeddaily maximum≤ 60 mg/Lall year003
Iron, total [as Fe]quarterly averagereport only (mg/L)all year003
Iron, total [as Fe]quarterly averagereport only (lb/d)all year003
Manganese, total [as Mn]quarterly averagereport only (mg/L)all year003
Manganese, total [as Mn]quarterly averagereport only (lb/d)all year003
Aluminum, total [as Al]quarterly averagereport only (mg/L)all year003
Aluminum, total [as Al]quarterly averagereport only (lb/d)all year003
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year003
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year003
Solids, total suspendedmonthly average≤ 30 mg/Lall year004
Solids, total suspendeddaily maximum≤ 60 mg/Lall year004
Iron, total [as Fe]quarterly averagereport only (mg/L)all year004
Iron, total [as Fe]quarterly averagereport only (lb/d)all year004
Manganese, total [as Mn]quarterly averagereport only (mg/L)all year004
Manganese, total [as Mn]quarterly averagereport only (lb/d)all year004
Aluminum, total [as Al]quarterly averagereport only (mg/L)all year004
Aluminum, total [as Al]quarterly averagereport only (lb/d)all year004
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year004
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year004

How strict are these limits?

Cited limits by parameter: Pennsylvania's rules and the federal ones.

Same industry: the 214 Water Supply permits in Pennsylvania.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/PA0260479 · MCP: https://passage-data.com/mcp