Gray Area Water Auth of Jenner TWP

Water Supply, Boswell, Pennsylvania. NPDES permit PA0255483, in force until Jul 31, 2029. Last 12 months: no values over a limit, 26 required values missing. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 28 days after each period: form A monthly (26 values)
Last report on file
June 2026
Oct 2024 – Sep 2025
6 values over a limit, 0 required values missing, 0 of 12 reports late

Limits in force (26)

ParameterStatisticLimitMonths
pHinstantaneous minimum≥ 6 SUall year
pHinstantaneous maximum≤ 9 SUall year
Solids, total suspendedmonthly average≤ 8.6 mg/Lall year
Solids, total suspendeddaily maximum≤ 13.4 mg/Lall year
Sulfate, total [as SO4]monthly averagereport only (mg/L)all year
Sulfate, total [as SO4]daily maximumreport only (mg/L)all year
Barium, total [as Ba]monthly averagereport only (ug/L)all year
Barium, total [as Ba]daily maximumreport only (ug/L)all year
Boron, total [as B]monthly averagereport only (ug/L)all year
Boron, total [as B]daily maximumreport only (ug/L)all year
Iron, total [as Fe]monthly average≤ 1.5 mg/Lall year
Iron, total [as Fe]daily maximum≤ 3 mg/Lall year
Iron, dissolved [as Fe]monthly average≤ 34.4 ug/Lall year
Iron, dissolved [as Fe]daily maximum≤ 53.6 ug/Lall year
Lead, total [as Pb]monthly averagereport only (ug/L)all year
Lead, total [as Pb]daily maximumreport only (ug/L)all year
Manganese, total [as Mn]monthly average≤ 1 mg/Lall year
Manganese, total [as Mn]daily maximum≤ 2 mg/Lall year
Aluminum, total [as Al]monthly average≤ .75 mg/Lall year
Aluminum, total [as Al]daily maximum≤ .75 mg/Lall year
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year
Chlorine, total residualmonthly average≤ .5 mg/Lall year
Chlorine, total residualdaily maximum≤ 1 mg/Lall year
Bromide [as Br]monthly average≤ 43 ug/Lall year
Bromide [as Br]daily maximum≤ 67 ug/Lall year

How strict are these limits?

Cited limits by parameter: Pennsylvania's rules and the federal ones.

Same industry: the 214 Water Supply permits in Pennsylvania.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/PA0255483 · MCP: https://passage-data.com/mcp