Passage Data · Check a report · Use it from your AI
Water Supply, Wellsboro, Pennsylvania. NPDES permit PA0229172, in force until Feb 28, 2030. Last 12 months: over a limit once (last February 2026), 14 required values missing, 1 of 10 reports late. Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| February 2026 | Chlorine, total residual, monthly average | .83 mg/L | ≤ .5 mg/L | 66% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| pH | instantaneous minimum | ≥ 6 SU | all year |
| pH | instantaneous maximum | ≤ 9 SU | all year |
| Solids, total suspended | monthly average | ≤ 30 mg/L | all year |
| Solids, total suspended | instantaneous maximum | ≤ 60 mg/L | all year |
| Iron, total [as Fe] | monthly average | ≤ 1.5 mg/L | all year |
| Iron, total [as Fe] | instantaneous maximum | ≤ 3 mg/L | all year |
| Manganese, total [as Mn] | monthly average | ≤ 1 mg/L | all year |
| Manganese, total [as Mn] | instantaneous maximum | ≤ 2 mg/L | all year |
| Aluminum, total [as Al] | monthly average | ≤ .75 mg/L | all year |
| Aluminum, total [as Al] | instantaneous maximum | ≤ 1.5 mg/L | all year |
| Flow, in conduit or thru treatment plant | monthly average | report only (MGD) | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Chlorine, total residual | monthly average | ≤ .5 mg/L | all year |
| Chlorine, total residual | instantaneous maximum | ≤ 1.6 mg/L | all year |
Cited limits by parameter: Pennsylvania's rules and the federal ones.
Same industry: the 214 Water Supply permits in Pennsylvania.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/PA0229172 · MCP: https://passage-data.com/mcp