Passage Data · Check a report · Use it from your AI

Highridge Water Auth

Water Supply, Fairfield Twp, Pennsylvania. NPDES permit PA0216895, in force until Apr 30, 2030. Last 12 months: no values over a limit, 34 required values missing. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 28 days after each period: outfall 001 form A monthly (1 value), outfall 002 form A monthly (16 values), outfall 003 form A monthly (17 values), outfall 001 form S twice a year
Last report on file
June 2026
Oct 2024 – Sep 2025
1 value over a limit, 0 required values missing, 1 of 24 reports late

Limits in force (46)

ParameterStatisticLimitMonthsOutfall
BOD, 5-day, 20 deg. Csemi-annual average≤ 10 mg/Lall year001
BOD, 5-day, 20 deg. Cinstantaneous maximum≤ 20 mg/Lall year001
pHinstantaneous minimum≥ 6 SUall year001
pHinstantaneous maximum≤ 9 SUall year001
Solids, total suspendedsemi-annual average≤ 10 mg/Lall year001
Solids, total suspendedinstantaneous maximum≤ 20 mg/Lall year001
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year001
Chlorine, total residualsemi-annual average≤ .5 mg/Lall year001
Chlorine, total residualinstantaneous maximum≤ 1.6 mg/Lall year001
Coliform, fecal generalsemi-annual average≤ 200 #/100mLJul–Dec001
Coliform, fecal generalsemi-annual average≤ 200 #/100mLJan–Jun001
Coliform, fecal generalinstantaneous maximumreport only (#/100mL)Jul–Dec001
Coliform, fecal generalinstantaneous maximumreport only (#/100mL)Jan–Jun001
pHinstantaneous minimum≥ 6 SUall year002
pHinstantaneous maximum≤ 9 SUall year002
Solids, total suspendedmonthly average≤ 30 mg/Lall year002
Solids, total suspendeddaily maximum≤ 60 mg/Lall year002
Cadmium, total [as Cd]monthly averagereport only (ug/L)all year002
Cadmium, total [as Cd]daily maximumreport only (ug/L)all year002
Iron, total [as Fe]monthly average≤ 1.5 mg/Lall year002
Iron, total [as Fe]daily maximum≤ 3 mg/Lall year002
Manganese, total [as Mn]monthly average≤ 1 mg/Lall year002
Manganese, total [as Mn]daily maximum≤ 2 mg/Lall year002
Aluminum, total [as Al]monthly average≤ .75 mg/Lall year002
Aluminum, total [as Al]daily maximum≤ .75 mg/Lall year002
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year002
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year002
Chlorine, total residualmonthly average≤ .5 mg/Lall year002
Chlorine, total residualdaily maximum≤ 1 mg/Lall year002
pHinstantaneous minimum≥ 6 SUall year003
pHinstantaneous maximum≤ 9 SUall year003
Solids, total suspendedmonthly average≤ 30 mg/Lall year003
Solids, total suspendeddaily maximum≤ 60 mg/Lall year003
Cadmium, total [as Cd]monthly averagereport only (ug/L)all year003
Cadmium, total [as Cd]daily maximumreport only (ug/L)all year003
Iron, total [as Fe]monthly average≤ 1.5 mg/Lall year003
Iron, total [as Fe]daily maximum≤ 3 mg/Lall year003
Manganese, total [as Mn]monthly average≤ 1 mg/Lall year003
Manganese, total [as Mn]daily maximum≤ 2 mg/Lall year003
Aluminum, total [as Al]monthly average≤ .75 mg/Lall year003
Aluminum, total [as Al]daily maximum≤ .75 mg/Lall year003
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year003
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year003
Chlorine, total residualmonthly average≤ .5 mg/Lall year003
Chlorine, total residualdaily maximum≤ 1 mg/Lall year003
Duration of dischargedaily maximumreport only (hr)all year003

How strict are these limits?

Cited limits by parameter: Pennsylvania's rules and the federal ones.

Same industry: the 214 Water Supply permits in Pennsylvania.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/PA0216895 · MCP: https://passage-data.com/mcp