Passage Data · Check a report · Use it from your AI

Bradford City Water Auth

Water Supply, Bradford, Pennsylvania. NPDES permit PA0101621, in force until Jul 31, 2030. Last 12 months: over a limit 4 times (last May 2026), 26 required values missing, 1 of 21 reports late. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 28 days after each period: outfall 001 form A monthly (22 values), outfall 002 form A monthly (4 values), outfall 002 form Y yearly
Last report on file
June 2026
Oct 2024 – Sep 2025
7 values over a limit, 0 required values missing, 1 of 25 reports late

Last 12 months (Oct 1, 2025 – Sep 30, 2026)

Period endingOutfallParameterReportedLimitOver by
October 2025001pH, daily minimum5.9 SU≥ 6 SU—
December 2025002BOD, 5-day, 20 deg. C, annual average19.8 mg/L≤ 10 mg/L98%
December 2025002Coliform, fecal general, annual average> 2420 #/100mL≤ 200 #/100mL—
May 2026001pH, daily minimum5.8 SU≥ 6 SU—

Limits in force (32)

ParameterStatisticLimitMonthsOutfall
pHdaily minimum≥ 6 SUall year001
pHdaily maximum≤ 9 SUall year001
Solids, total suspendedmonthly average≤ 30 mg/Lall year001
Solids, total suspendeddaily maximum≤ 60 mg/Lall year001
Solids, total suspendedmonthly averagereport only (lb/d)all year001
Solids, total suspendeddaily maximumreport only (lb/d)all year001
Iron, total [as Fe]monthly average≤ 2 mg/Lall year001
Iron, total [as Fe]daily maximum≤ 4 mg/Lall year001
Iron, total [as Fe]monthly averagereport only (lb/d)all year001
Iron, total [as Fe]daily maximumreport only (lb/d)all year001
Manganese, total [as Mn]monthly average≤ 1 mg/Lall year001
Manganese, total [as Mn]daily maximum≤ 2 mg/Lall year001
Manganese, total [as Mn]monthly averagereport only (lb/d)all year001
Manganese, total [as Mn]daily maximumreport only (lb/d)all year001
Aluminum, total [as Al]monthly average≤ 1.5 mg/Lall year001
Aluminum, total [as Al]daily maximum≤ 3 mg/Lall year001
Aluminum, total [as Al]monthly average≤ 1.9 lb/dall year001
Aluminum, total [as Al]daily maximum≤ 3.7 lb/dall year001
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year001
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year001
Chlorine, total residualmonthly average≤ .1 mg/Lall year001
Chlorine, total residualinstantaneous maximum≤ .25 mg/Lall year001
BOD, 5-day, 20 deg. Cannual average≤ 10 mg/Lall year002
BOD, 5-day, 20 deg. Cinstantaneous maximum≤ 20 mg/Lall year002
pHinstantaneous minimum≥ 6 SUall year002
pHinstantaneous maximum≤ 9 SUall year002
Solids, total suspendedannual average≤ 10 mg/Lall year002
Solids, total suspendedinstantaneous maximum≤ 20 mg/Lall year002
Flow, in conduit or thru treatment plantannual averagereport only (MGD)all year002
Chlorine, total residualmonthly average≤ .5 mg/Lall year002
Chlorine, total residualinstantaneous maximum≤ 1.2 mg/Lall year002
Coliform, fecal generalannual average≤ 200 #/100mLall year002

How strict are these limits?

Cited limits by parameter: Pennsylvania's rules and the federal ones.

Same industry: the 214 Water Supply permits in Pennsylvania.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/PA0101621 · MCP: https://passage-data.com/mcp