Passage Data · Check a report · Use it from your AI

Greater Johnstown Water Auth

Water Supply, Johnstown, Pennsylvania. NPDES permit PA0095010, in force until Jun 30, 2028. Last 12 months: no values over a limit. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 28 days after each period: outfall 001 form A monthly (14 values), outfall 002 form S twice a year, outfall 003 form S twice a year
Renewal application due
Jan 2, 2028 · 180 days before expiry; your permit may set another date
Last report on file
July 2026
Oct 2024 – Sep 2025
4 values over a limit, 0 required values missing, 0 of 16 reports late

Limits in force (32)

ParameterStatisticLimitMonthsOutfall
pHdaily minimum≥ 6 SUall year001
pHinstantaneous maximum≤ 9 SUall year001
Solids, total suspendedmonthly average≤ 30 mg/Lall year001
Solids, total suspendeddaily maximum≤ 60 mg/Lall year001
Iron, total [as Fe]monthly average≤ 1.5 mg/Lall year001
Iron, total [as Fe]daily maximum≤ 3 mg/Lall year001
Manganese, total [as Mn]monthly average≤ 1 mg/Lall year001
Manganese, total [as Mn]daily maximum≤ 2 mg/Lall year001
Aluminum, total [as Al]monthly average≤ .75 mg/Lall year001
Aluminum, total [as Al]daily maximum≤ 1.5 mg/Lall year001
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year001
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year001
Chlorine, total residualmonthly average≤ .5 mg/Lall year001
Chlorine, total residualinstantaneous maximum≤ 1 mg/Lall year001
Oxygen demand, chem. [high level] [COD]daily maximumreport only (mg/L)all year002
pHdaily maximumreport only (SU)all year002
Solids, total suspendeddaily maximumreport only (mg/L)all year002
Oil & Greasedaily maximumreport only (mg/L)all year002
Nitrogen, total [as N]daily maximumreport only (mg/L)all year002
Phosphorus, total [as P]daily maximumreport only (mg/L)all year002
Iron, total [as Fe]daily maximumreport only (mg/L)all year002
Manganese, total [as Mn]daily maximumreport only (mg/L)all year002
Aluminum, total [as Al]daily maximumreport only (mg/L)all year002
Oxygen demand, chem. [high level] [COD]daily maximumreport only (mg/L)all year003
pHdaily maximumreport only (SU)all year003
Solids, total suspendeddaily maximumreport only (mg/L)all year003
Oil & Greasedaily maximumreport only (mg/L)all year003
Nitrogen, total [as N]daily maximumreport only (mg/L)all year003
Phosphorus, total [as P]daily maximumreport only (mg/L)all year003
Iron, total [as Fe]daily maximumreport only (mg/L)all year003
Manganese, total [as Mn]daily maximumreport only (mg/L)all year003
Aluminum, total [as Al]daily maximumreport only (mg/L)all year003

How strict are these limits?

Cited limits by parameter: Pennsylvania's rules and the federal ones.

Same industry: the 214 Water Supply permits in Pennsylvania.