Passage Data · Check a report · Use it from your AI

Tamaqua Boro Area Water Auth Schuylkill Cnty

Water Supply, Tamaqua, Pennsylvania. NPDES permit PA0063053, in force until Dec 31, 2030. Last 12 months: over a limit 9 times (last January 2026), 17 required values missing. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 28 days after each period: form A monthly (17 values)
Last report on file
June 2026
Oct 2024 – Sep 2025
4 values over a limit, 0 required values missing, 1 of 12 reports late

Last 12 months (Oct 1, 2025 – Sep 30, 2026)

Period endingParameterReportedLimitOver by
December 2025Iron, total [as Fe], daily maximum4.8 mg/L≤ 4 mg/L20%
December 2025Manganese, total [as Mn], daily maximum3.4 mg/L≤ 2 mg/L70%
December 2025Manganese, total [as Mn], monthly average2≤ 1.58 lb/d27%
January 2026Iron, total [as Fe], daily maximum8.2 mg/L≤ 4 mg/L105%
January 2026Iron, total [as Fe], monthly average5 mg/L≤ 2 mg/L150%
January 2026Iron, total [as Fe], monthly average8≤ 3.17 lb/d152%
January 2026Manganese, total [as Mn], daily maximum7.2 mg/L≤ 2 mg/L260%
January 2026Manganese, total [as Mn], monthly average4.3 mg/L≤ 1 mg/L330%
January 2026Manganese, total [as Mn], monthly average7≤ 1.58 lb/d343%

Limits in force (17)

ParameterStatisticLimitMonths
pHinstantaneous minimum≥ 6 SUall year
pHinstantaneous maximum≤ 9 SUall year
Solids, total suspendedmonthly average≤ 30 mg/Lall year
Solids, total suspendeddaily maximum≤ 60 mg/Lall year
Iron, total [as Fe]monthly average≤ 2 mg/Lall year
Iron, total [as Fe]daily maximum≤ 4 mg/Lall year
Iron, total [as Fe]monthly average≤ 3.17 lb/dall year
Manganese, total [as Mn]monthly average≤ 1 mg/Lall year
Manganese, total [as Mn]daily maximum≤ 2 mg/Lall year
Manganese, total [as Mn]monthly average≤ 1.58 lb/dall year
Aluminum, total [as Al]monthly average≤ 3.7 mg/Lall year
Aluminum, total [as Al]daily maximum≤ 5.7 mg/Lall year
Aluminum, total [as Al]monthly average≤ 5.86 lb/dall year
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year
Chlorine, total residualmonthly average≤ .5 mg/Lall year
Chlorine, total residualdaily maximum≤ 1 mg/Lall year

How strict are these limits?

Cited limits by parameter: Pennsylvania's rules and the federal ones.

Same industry: the 214 Water Supply permits in Pennsylvania.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history