Passage Data · Check a report · Use it from your AI
Water Supply, Troy, Pennsylvania. NPDES permit PA0060305, in force until Dec 31, 2027. Last 12 months: over a limit once (last April 2026), 8 required values missing. Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| April 2026 | Solids, total suspended, monthly average | 47 mg/L | ≤ 30 mg/L | 57% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| pH | instantaneous minimum | ≥ 6 SU | all year |
| pH | instantaneous maximum | ≤ 9 SU | all year |
| Solids, total suspended | monthly average | ≤ 30 mg/L | all year |
| Solids, total suspended | instantaneous maximum | ≤ 60 mg/L | all year |
| Iron, total [as Fe] | annual average | ≤ 2 mg/L | all year |
| Iron, total [as Fe] | daily maximum | ≤ 4 mg/L | all year |
| Manganese, total [as Mn] | annual average | ≤ 1 mg/L | all year |
| Manganese, total [as Mn] | daily maximum | ≤ 2 mg/L | all year |
| Aluminum, total [as Al] | annual average | ≤ 4 mg/L | all year |
| Aluminum, total [as Al] | daily maximum | ≤ 8 mg/L | all year |
| Flow, in conduit or thru treatment plant | monthly average | report only (MGD) | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Chlorine, total residual | monthly average | ≤ .5 mg/L | all year |
| Chlorine, total residual | instantaneous maximum | ≤ 1.2 mg/L | all year |
Cited limits by parameter: Pennsylvania's rules and the federal ones.
Same industry: the 214 Water Supply permits in Pennsylvania.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/PA0060305 · MCP: https://passage-data.com/mcp