Passage Data · Check a report · Use it from your AI

Easton Suburban Water Auth

Water Supply, Easton, Pennsylvania. NPDES permit PA0051632, in force until Nov 30, 2027. Last 12 months: no values over a limit. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 28 days after each period: outfall 001 form A monthly (17 values), outfall 002 form A monthly (15 values)
Renewal application due
Jun 3, 2027 · 180 days before expiry; your permit may set another date
Last report on file
July 2026
Oct 2024 – Sep 2025
2 values over a limit, 0 required values missing, 0 of 24 reports late

Limits in force (32)

ParameterStatisticLimitMonthsOutfall
Turbiditydaily maximum≤ 100 NTUall year001
pHinstantaneous minimum≥ 6 SUall year001
pHinstantaneous maximum≤ 9 SUall year001
Solids, total suspendedmonthly average≤ 30 mg/Lall year001
Solids, total suspendeddaily maximum≤ 60 mg/Lall year001
Iron, total [as Fe]monthly average≤ 2 mg/Lall year001
Iron, total [as Fe]daily maximum≤ 4 mg/Lall year001
Manganese, total [as Mn]monthly average≤ 1 mg/Lall year001
Manganese, total [as Mn]daily maximum≤ 2 mg/Lall year001
Aluminum, total [as Al]monthly average≤ 4 mg/Lall year001
Aluminum, total [as Al]daily maximum≤ 8 mg/Lall year001
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year001
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year001
Chlorine, total residualmonthly average≤ .5 mg/Lall year001
Chlorine, total residualinstantaneous maximum≤ .75 mg/Lall year001
Duration of dischargemonthly averagereport only (hr)all year001
Duration of dischargemonthly totalreport only (hr)all year001
Turbiditydaily maximum≤ 100 NTUall year002
pHinstantaneous minimum≥ 6 SUall year002
pHinstantaneous maximum≤ 9 SUall year002
Solids, total suspendedmonthly average≤ 30 mg/Lall year002
Solids, total suspendeddaily maximum≤ 60 mg/Lall year002
Iron, total [as Fe]monthly average≤ 2 mg/Lall year002
Iron, total [as Fe]daily maximum≤ 4 mg/Lall year002
Manganese, total [as Mn]monthly average≤ 1 mg/Lall year002
Manganese, total [as Mn]daily maximum≤ 2 mg/Lall year002
Aluminum, total [as Al]monthly average≤ 4 mg/Lall year002
Aluminum, total [as Al]daily maximum≤ 8 mg/Lall year002
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year002
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year002
Chlorine, total residualmonthly average≤ .5 mg/Lall year002
Chlorine, total residualinstantaneous maximum≤ .75 mg/Lall year002

How strict are these limits?

Cited limits by parameter: Pennsylvania's rules and the federal ones.

Same industry: the 214 Water Supply permits in Pennsylvania.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/PA0051632 · MCP: https://passage-data.com/mcp