Water Supply, Columbiana, Ohio. NPDES permit OH0030881, in force until Dec 31, 2026. Last 12 months: no values over a limit. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 20 days after each period: outfall 003 form A monthly (27 values), outfall 901 form A monthly (4 values)
Renewal application due
Jul 4, 2026 · 180 days before expiry; your permit may set another date
Last report on file
August 2026
Oct 2024 – Sep 2025
0 values over a limit, 0 required values missing, 0 of 24 reports late

Limits in force (31)

ParameterStatisticLimitMonthsOutfall
pHdaily minimum≥ 6.5 SUall year003
pHdaily maximum≤ 11 SUall year003
Solids, total suspendedmonthly average≤ 15 mg/Lall year003
Solids, total suspendeddaily maximum≤ 20 mg/Lall year003
Solids, total suspendedmonthly average≤ 3.7 kg/dall year003
Solids, total suspendeddaily maximum≤ 4.9 kg/dall year003
Dichlorobromomethanemonthly averagereport only (ug/L)Sep003
Dichlorobromomethanedaily maximumreport only (ug/L)Sep003
Bromoformmonthly averagereport only (ug/L)Sep003
Bromoformdaily maximumreport only (ug/L)Sep003
Dibromochloromethanemonthly averagereport only (ug/L)Sep003
Dibromochloromethanedaily maximumreport only (ug/L)Sep003
Chloroformmonthly averagereport only (ug/L)Sep003
Chloroformdaily maximumreport only (ug/L)Sep003
Methyl bromide [Bromomethane]monthly averagereport only (ug/L)Sep003
Methyl bromide [Bromomethane]daily maximumreport only (ug/L)Sep003
Methyl chloride [Chloromethane]monthly averagereport only (ug/L)Sep003
Methyl chloride [Chloromethane]daily maximumreport only (ug/L)Sep003
Methylene chloridemonthly averagereport only (ug/L)Sep003
Methylene chloridedaily maximumreport only (ug/L)Sep003
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year003
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year003
Chlorine, total residualdaily maximum≤ .019 mg/Lall year003
Microcystinmonthly averagereport only (ug/L)all year003
Microcystindaily maximumreport only (ug/L)all year003
Solids, total dissolved- 180 deg. Cmonthly averagereport only (mg/L)all year003
Solids, total dissolved- 180 deg. Cdaily maximumreport only (mg/L)all year003
pHdaily minimumreport only (SU)all year901
pHdaily maximumreport only (SU)all year901
Turbidity [severity]monthly averagereport only (severity)all year901
Turbidity [severity]daily maximumreport only (severity)all year901

How strict are these limits?

Cited limits by parameter: Ohio's rules and the federal ones.

Same industry: the 147 Water Supply permits in Ohio.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/OH0030881 · MCP: https://passage-data.com/mcp