Passage Data · Check a report · Use it from your AI

Ashland WTP

Water Supply, Ashland, Ohio. NPDES permit OH0008991, in force until May 31, 2030. Last 12 months: over a limit 2 times (last September 2026), 4 required values missing. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 20 days after each period: outfall 001 form A monthly (11 values), outfall 002 form A monthly (11 values), outfall 003 form A monthly (11 values)
Last report on file
September 2026
Oct 2024 – Sep 2025
1 value over a limit, 0 required values missing, 6 of 36 reports late

Last 12 months (Oct 1, 2025 – Sep 30, 2026)

Period endingParameterReportedLimitOver by
September 2026Solids, total suspended, daily maximum60≤ 45 mg/L33%
September 2026Solids, total suspended, monthly average57≤ 30 mg/L90%

Limits in force (33)

ParameterStatisticLimitMonthsOutfall
pHdaily minimum≥ 6.5 SUall year001
pHdaily maximum≤ 10 SUall year001
Solids, total suspendedmonthly average≤ 30 mg/Lall year001
Solids, total suspendeddaily maximum≤ 45 mg/Lall year001
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year001
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year001
Chlorine, total residualdaily maximum≤ .019 mg/Lall year001
Solids, total dissolved- 180 deg. Cmonthly averagereport only (mg/L)all year001
Solids, total dissolved- 180 deg. Cdaily maximumreport only (mg/L)all year001
Trihalomethane, tot.monthly averagereport only (ug/L)Sep001
Trihalomethane, tot.daily maximumreport only (ug/L)Sep001
pHdaily minimum≥ 6.5 SUall year002
pHdaily maximum≤ 10 SUall year002
Solids, total suspendedmonthly average≤ 30 mg/Lall year002
Solids, total suspendeddaily maximum≤ 45 mg/Lall year002
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year002
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year002
Chlorine, total residualdaily maximum≤ .019 mg/Lall year002
Solids, total dissolved- 180 deg. Cmonthly averagereport only (mg/L)all year002
Solids, total dissolved- 180 deg. Cdaily maximumreport only (mg/L)all year002
Trihalomethane, tot.monthly averagereport only (ug/L)Sep002
Trihalomethane, tot.daily maximumreport only (ug/L)Sep002
pHdaily minimum≥ 6.5 SUall year003
pHdaily maximum≤ 10 SUall year003
Solids, total suspendedmonthly average≤ 30 mg/Lall year003
Solids, total suspendeddaily maximum≤ 45 mg/Lall year003
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year003
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year003
Chlorine, total residualdaily maximum≤ .019 mg/Lall year003
Solids, total dissolved- 180 deg. Cmonthly averagereport only (mg/L)all year003
Solids, total dissolved- 180 deg. Cdaily maximumreport only (mg/L)all year003
Trihalomethane, tot.monthly averagereport only (ug/L)Sep003
Trihalomethane, tot.daily maximumreport only (ug/L)Sep003

How strict are these limits?

Cited limits by parameter: Ohio's rules and the federal ones.

Same industry: the 147 Water Supply permits in Ohio.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/OH0008991 · MCP: https://passage-data.com/mcp