Water Supply, Logan, Ohio. NPDES permit OH0008656, in force until Apr 30, 2028. Last 12 months: over a limit once (last March 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| March 2026 | Toxicity [acute], Ceriodaphnia dubia, daily maximum | 2.4 | ≤ 1 tox acute | 140% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Temperature, water deg. centigrade | monthly average | report only (deg C) | all year |
| Temperature, water deg. centigrade | daily maximum | report only (deg C) | all year |
| Oxygen, dissolved [DO] | daily minimum | ≥ 6 mg/L | all year |
| pH | daily minimum | ≥ 6.5 SU | all year |
| pH | daily maximum | ≤ 9 SU | all year |
| Solids, total suspended | monthly average | ≤ 12 mg/L | all year |
| Solids, total suspended | daily maximum | ≤ 18 mg/L | all year |
| Solids, total suspended | monthly average | ≤ 28.4 kg/d | all year |
| Solids, total suspended | daily maximum | ≤ 42.6 kg/d | all year |
| Iron, suspended | monthly average | ≤ 1000 ug/L | all year |
| Iron, suspended | daily maximum | ≤ 2000 ug/L | all year |
| Iron, suspended | monthly average | ≤ 2.37 kg/d | all year |
| Iron, suspended | daily maximum | ≤ 4.74 kg/d | all year |
| Manganese, suspended | monthly average | ≤ 1000 ug/L | all year |
| Manganese, suspended | daily maximum | ≤ 2000 ug/L | all year |
| Manganese, suspended | monthly average | ≤ 2.37 kg/d | all year |
| Manganese, suspended | daily maximum | ≤ 4.74 kg/d | all year |
| Strontium, total recoverable, ug/L | monthly average | report only (ug/L) | all year |
| Strontium, total recoverable, ug/L | daily maximum | report only (ug/L) | all year |
| Flow, in conduit or thru treatment plant | monthly average | report only (MGD) | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Chlorine, total residual | daily maximum | ≤ .038 mg/L | all year |
| Toxicity [acute], Ceriodaphnia dubia | daily maximum | ≤ 1 tox acute | Mar, Sep |
| Solids, total dissolved- 180 deg. C | monthly average | report only (mg/L) | all year |
| Solids, total dissolved- 180 deg. C | daily maximum | report only (mg/L) | all year |
Cited limits by parameter: Ohio's rules and the federal ones.