Water Supply, Earlton, New York. NPDES permit NY0261076, in force until Sep 30, 2029. Last 12 months: over a limit 5 times (last September 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| November 2025 | Flow rate, monthly average | .27 MGD | ≤ .25 MGD | 8% |
| August 2026 | Flow rate, monthly average | .31 MGD | ≤ .25 MGD | 24% |
| September 2026 | Aluminum, total [as Al], daily maximum | 4.67 mg/L | ≤ 4 mg/L | 17% |
| September 2026 | Aluminum, total [as Al], monthly average | 4.67 mg/L | ≤ 2 mg/L | 134% |
| September 2026 | Solids, total suspended, monthly average | 27 mg/L | ≤ 20 mg/L | 35% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Temperature, water deg. fahrenheit | daily maximum | ≤ 70 deg F (alert, not enforceable) | all year |
| Flow rate | monthly average | ≤ .25 MGD | all year |
| pH | minimum | ≥ 6.5 SU | all year |
| pH | maximum | ≤ 8.5 SU | all year |
| Solids, total suspended | monthly average | ≤ 20 mg/L | all year |
| Solids, total suspended | daily maximum | ≤ 40 mg/L | all year |
| Solids, settleable | daily maximum | ≤ .1 mL/L | all year |
| Iron, total [as Fe] | monthly average | ≤ 2 mg/L | all year |
| Iron, total [as Fe] | daily maximum | ≤ 4 mg/L | all year |
| Aluminum, total [as Al] | monthly average | ≤ 2 mg/L | all year |
| Aluminum, total [as Al] | daily maximum | ≤ 4 mg/L | all year |
| Chlorine, total residual | daily maximum | ≤ .1 mg/L | all year |
Cited limits by parameter: New York's rules and the federal ones.
Same industry: the 53 Water Supply permits in New York.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/NY0261076 · MCP: https://passage-data.com/mcp