Nonclassifiable Establishments, Albany, New York. NPDES permit NY0104060, in force until Jul 31, 2029. Last 12 months: over a limit 3 times (last September 2026), 12 required values missing, 3 of 12 reports late. Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| July 2026 | Temperature, water deg. fahrenheit, maximum | 95.7 deg F | ≤ 90 deg F | 6% |
| August 2026 | Temperature, water deg. fahrenheit, maximum | 95 deg F | ≤ 90 deg F | 6% |
| September 2026 | Temperature, water deg. fahrenheit, maximum | 90.3 deg F | ≤ 90 deg F | 0% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Temperature, water deg. fahrenheit | monthly average | report only (deg F) | all year |
| Temperature, water deg. fahrenheit | monthly average | report only (deg F) | all year |
| Temperature, water deg. fahrenheit | maximum | ≤ 90 deg F | all year |
| pH | minimum | ≥ 6.5 SU | all year |
| pH | maximum | ≤ 8.5 SU | all year |
| Flow, in conduit or thru treatment plant | monthly average | report only (MGD) | all year |
| Flow, in conduit or thru treatment plant | daily maximum | ≤ 92 MGD | all year |
| Chlorine, total residual | monthly average | report only (mg/L) | all year |
| Chlorine, total residual | daily maximum | ≤ .2 mg/L | all year |
| Temp. diff. between intake and discharge | monthly average | report only (deg F) | all year |
| Temp. diff. between intake and discharge | daily maximum | ≤ 24 deg F | all year |
Cited limits by parameter: New York's rules and the federal ones.
Same industry: the 23 Nonclassifiable Establishments permits in New York.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/NY0104060 · MCP: https://passage-data.com/mcp